CVE-2025-24481
FactoryTalk® View Site Edition - Incorrect Permission Assignment
Mitigation
- Vendor workaround: Protect physical access to the workstation & restrict access to port 8091 at the network or workstation.
Who should check
- Anyone running Rockwell Automation FactoryTalk® View Site Edition <V15
Vulnerability facts
- Affected
- Rockwell Automation FactoryTalk® View Site Edition <V15
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 7.0 (v4.0, CNA)CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
- Attack vector: Local
- Attack complexity: Low
- Attack requirements: None
- Privileges required: None
- User interaction: None
- Confidentiality impact: Low
- Integrity impact: Low
- Availability impact: High
- Confidentiality impact on other systems: None
- Integrity impact on other systems: None
- Availability impact on other systems: None
- EPSS
- 0.26% chance of exploitation in 30 days (percentile 11, 2026-11-26)
- CWE
- CWE-732
- Modified
Description
An Incorrect Permission Assignment Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect permissions being assigned to the remote debugger port and can allow for unauthenticated access to the system configuration.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Rockwell Automation FactoryTalk® View Site Edition | <V15 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2025-24481. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2025-24481.md Affected: Rockwell Automation FactoryTalk® View Site Edition <V15 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Rockwell Automation FactoryTalk® View Site Edition: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2025-24481 being exploited?
There is no confirmed exploitation: CVE-2025-24481 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.26% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2025-24481?
High: CVSS 7.0 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed).
Which versions are affected by CVE-2025-24481?
Rockwell Automation FactoryTalk® View Site Edition <V15.
Is there a fix for CVE-2025-24481?
No fixed version is listed in the sources yet. Vendor workaround: Protect physical access to the workstation & restrict access to port 8091 at the network or workstation.
How do I check if I'm affected by CVE-2025-24481?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.