CVE-2026-8066
A directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 end-of-life versions allo…
Mitigation
- Upgrade RTU500 series CMU firmware to 12.0 or later.
Who should check
- Anyone running Hitachi Energy RTU500 series CMU firmware >= 9.0, < 12.0
Vulnerability facts
- Affected
- Hitachi Energy RTU500 series CMU firmware >= 9.0, < 12.0
- Fixed in
- Hitachi Energy RTU500 series CMU firmware 12.0
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.1 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: High
- Availability impact: High
- EPSS
- 1.16% chance of exploitation in 30 days (percentile 67, 2026-11-26)
- CWE
- CWE-23
- Modified
Description
A directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 end-of-life versions allows an unauthenticated attacker to write or overwrite arbitrary files on the device file system. Depending on the files affected, successful exploitation could result in unauthorized modification of device data or disruption of the device’s intended operation.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Hitachi Energy RTU500 series CMU firmware | >= 9.0, < 12.0 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2026-8066. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2026-8066.md Affected: Hitachi Energy RTU500 series CMU firmware >= 9.0, < 12.0 Fixed in: Hitachi Energy RTU500 series CMU firmware 12.0 Steps: 1. Search this machine and project for Hitachi Energy RTU500 series CMU firmware: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2026-8066 being exploited?
There is no confirmed exploitation: CVE-2026-8066 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.16% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2026-8066?
Critical: CVSS 9.1 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2026-8066?
Hitachi Energy RTU500 series CMU firmware >= 9.0, < 12.0.
Is there a fix for CVE-2026-8066?
Yes. Fixed in Hitachi Energy RTU500 series CMU firmware 12.0. Upgrade RTU500 series CMU firmware to 12.0 or later.
How do I check if I'm affected by CVE-2026-8066?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.