CVE-2026-79625
Improper Synchronization in Monitoring in CODESYS Control Runtime
Mitigation
- Upgrade Control RTE (SL) to 3.5.22.40 or later.
- Upgrade Control RTE (for Beckhoff CX) SL to 3.5.22.40 or later.
- Upgrade Control Win (SL) to 3.5.22.40 or later.
- Upgrade Runtime Toolkit to 3.5.22.40 or later.
- Upgrade Safety SIL2 to 3.5.22.40 or later.
- Upgrade HMI (SL) to 3.5.22.40 or later.
- Upgrade Development System 3 to 3.5.22.40 or later.
- Upgrade Control for BeagleBone SL to 4.23.0.0 or later.
Who should check
- Anyone running CODESYS Control RTE (SL) >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Control RTE (for Beckhoff CX) SL >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Control Win (SL) >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Runtime Toolkit >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Safety SIL2 >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS HMI (SL) >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Development System 3 >= 3.0.0.0, < 3.5.22.40
- Anyone running CODESYS Control for BeagleBone SL >= 3.5.0.0, < 4.23.0.0
Vulnerability facts
- Affected
- CODESYS Control RTE (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.0.0.0, < 3.5.22.40; CODESYS Control Win (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Runtime Toolkit >= 3.0.0.0, < 3.5.22.40; CODESYS Safety SIL2 >= 3.0.0.0, < 3.5.22.40; CODESYS HMI (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Development System 3 >= 3.0.0.0, < 3.5.22.40; CODESYS Control for BeagleBone SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for emPC-A/iMX6 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for IOT2000 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Linux ARM SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Linux SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PFC100 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PFC200 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PLCnext SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Raspberry Pi SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for WAGO Touch Panels 600 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Virtual Control SL >= 3.5.0.0, < 4.23.0.0
- Fixed in
- CODESYS Control RTE (SL) 3.5.22.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.22.40, CODESYS Control Win (SL) 3.5.22.40, CODESYS Runtime Toolkit 3.5.22.40, CODESYS Safety SIL2 3.5.22.40, CODESYS HMI (SL) 3.5.22.40, CODESYS Development System 3 3.5.22.40, CODESYS Control for BeagleBone SL 4.23.0.0, CODESYS Control for emPC-A/iMX6 SL 4.23.0.0, CODESYS Control for IOT2000 SL 4.23.0.0, CODESYS Control for Linux ARM SL 4.23.0.0, CODESYS Control for Linux SL 4.23.0.0, CODESYS Control for PFC100 SL 4.23.0.0, CODESYS Control for PFC200 SL 4.23.0.0, CODESYS Control for PLCnext SL 4.23.0.0, CODESYS Control for Raspberry Pi SL 4.23.0.0, CODESYS Control for WAGO Touch Panels 600 SL 4.23.0.0, CODESYS Virtual Control SL 4.23.0.0
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, login needed
- CVSS
- 7.2 (v4.0, CNA)CVSS:4.0/AV:N/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Attack requirements: None
- Privileges required: Low
- User interaction: None
- Confidentiality impact: None
- Integrity impact: High
- Availability impact: High
- Confidentiality impact on other systems: None
- Integrity impact on other systems: None
- Availability impact on other systems: None
- EPSS
- 0.40% chance of exploitation in 30 days (percentile 26, 2026-11-26)
- CWE
- CWE-362
- Modified
Description
Affected products do not properly synchronize access to their monitoring functionality. When multiple clients send concurrent requests, this may lead to incorrect reads or writes, or to corruption of internal memory structures. An authenticated remote attacker with monitoring access can exploit this issue to cause incorrect data processing or a denial-of-service condition.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| CODESYS Control RTE (SL) | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Control RTE (for Beckhoff CX) SL | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Control Win (SL) | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Runtime Toolkit | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Safety SIL2 | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS HMI (SL) | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Development System 3 | >= 3.0.0.0, < 3.5.22.40 | — | cvelist |
| CODESYS Control for BeagleBone SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for emPC-A/iMX6 SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for IOT2000 SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for Linux ARM SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for Linux SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for PFC100 SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for PFC200 SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for PLCnext SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for Raspberry Pi SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Control for WAGO Touch Panels 600 SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
| CODESYS Virtual Control SL | >= 3.5.0.0, < 4.23.0.0 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2026-79625. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2026-79625.md Affected: CODESYS Control RTE (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.0.0.0, < 3.5.22.40; CODESYS Control Win (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Runtime Toolkit >= 3.0.0.0, < 3.5.22.40; CODESYS Safety SIL2 >= 3.0.0.0, < 3.5.22.40; CODESYS HMI (SL) >= 3.0.0.0, < 3.5.22.4… Fixed in: CODESYS Control RTE (SL) 3.5.22.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.22.40, CODESYS Control Win (SL) 3.5.22.40, CODESYS Runtime Toolkit 3.5.22.40, CODESYS Safety SIL2 3.5.22.40, CODESYS HMI (SL) 3.5.22.40, CODESYS Development System 3 3.5.22.40, CODESYS Control for BeagleBone SL 4.23.0.… Steps: 1. Search this machine and project for CODESYS Control RTE (SL), CODESYS Control RTE (for Beckhoff CX) SL, CODESYS Control Win (SL), CODESYS Runtime Toolkit, CODESYS Safety SIL2, CODESYS HMI (SL): dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2026-79625 being exploited?
There is no confirmed exploitation: CVE-2026-79625 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.40% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2026-79625?
High: CVSS 7.2 (v4.0, scored by CNA). Remote, login needed.
Which versions are affected by CVE-2026-79625?
CODESYS Control RTE (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.0.0.0, < 3.5.22.40; CODESYS Control Win (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Runtime Toolkit >= 3.0.0.0, < 3.5.22.40; CODESYS Safety SIL2 >= 3.0.0.0, < 3.5.22.40; CODESYS HMI (SL) >= 3.0.0.0, < 3.5.22.40; CODESYS Development System 3 >= 3.0.0.0, < 3.5.22.40; CODESYS Control for BeagleBone SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for emPC-A/iMX6 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for IOT2000 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Linux ARM SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Linux SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PFC100 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PFC200 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for PLCnext SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for Raspberry Pi SL >= 3.5.0.0, < 4.23.0.0; CODESYS Control for WAGO Touch Panels 600 SL >= 3.5.0.0, < 4.23.0.0; CODESYS Virtual Control SL >= 3.5.0.0, < 4.23.0.0.
Is there a fix for CVE-2026-79625?
Yes. Fixed in CODESYS Control RTE (SL) 3.5.22.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.22.40, CODESYS Control Win (SL) 3.5.22.40, CODESYS Runtime Toolkit 3.5.22.40, CODESYS Safety SIL2 3.5.22.40, CODESYS HMI (SL) 3.5.22.40, CODESYS Development System 3 3.5.22.40, CODESYS Control for BeagleBone SL 4.23.0.0, CODESYS Control for emPC-A/iMX6 SL 4.23.0.0, CODESYS Control for IOT2000 SL 4.23.0.0, CODESYS Control for Linux ARM SL 4.23.0.0, CODESYS Control for Linux SL 4.23.0.0, CODESYS Control for PFC100 SL 4.23.0.0, CODESYS Control for PFC200 SL 4.23.0.0, CODESYS Control for PLCnext SL 4.23.0.0, CODESYS Control for Raspberry Pi SL 4.23.0.0, CODESYS Control for WAGO Touch Panels 600 SL 4.23.0.0, CODESYS Virtual Control SL 4.23.0.0. Upgrade Control RTE (SL) to 3.5.22.40 or later. Upgrade Control RTE (for Beckhoff CX) SL to 3.5.22.40 or later. Upgrade Control Win (SL) to 3.5.22.40 or later. Upgrade Runtime Toolkit to 3.5.22.40 or later. Upgrade Safety SIL2 to 3.5.22.40 or later. Upgrade HMI (SL) to 3.5.22.40 or later. Upgrade Development System 3 to 3.5.22.40 or later. Upgrade Control for BeagleBone SL to 4.23.0.0 or later.
How do I check if I'm affected by CVE-2026-79625?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.