# CVE-2026-58114: A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions…

- **Severity:** HIGH 7.7
- **CVSS:** 7.7 (v4.0, CNA) `CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Attack requirements: Present; Privileges required: None; User interaction: Passive; Confidentiality impact: High; Integrity impact: High; Availability impact: High; Confidentiality impact on other systems: None; Integrity impact on other systems: None; Availability impact on other systems: None
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 0.52% (percentile 37, 2026-11-28)
- **CWE:** CWE-1390
- **Published:** 2026-11-10T11:30:33.284Z
- **Modified:** 2026-11-12T22:09:39.233Z

## Who should check

- Anyone running Siemens SIMATIC BATCH V9.1 \< \*
- Anyone running Siemens SIMATIC Information Server 2020 \< \*
- Anyone running Siemens SIMATIC Information Server 2022 \< \*
- Anyone running Siemens SIMATIC PCS 7 V9.1 \< \*
- Anyone running Siemens SIMATIC Process Historian 2020 \< \*
- Anyone running Siemens SIMATIC Process Historian 2022 \< \*
- Anyone running Siemens SIMATIC WinCC Runtime Professional V17 \< \*
- Anyone running Siemens SIMATIC WinCC Runtime Professional V18 \< \*

## Description

A vulnerability has been identified in SIMATIC BATCH V9.1 (All versions), SIMATIC Information Server 2020 (All versions), SIMATIC Information Server 2022 (All versions), SIMATIC PCS 7 V9.1 (All versions), SIMATIC Process Historian 2020 (All versions), SIMATIC Process Historian 2022 (All versions), SIMATIC WinCC Runtime Professional V17 (All versions), SIMATIC WinCC Runtime Professional V18 (All versions), SIMATIC WinCC Runtime Professional V19 (All versions), SIMATIC WinCC Runtime Professional V20 (All versions), SIMATIC WinCC Runtime Professional V21 (All versions), SIMATIC WinCC V7.5 (All versions), SIMATIC WinCC V8.0 (All versions), SIMATIC WinCC V8.1 (All versions). Affected systems do not properly secure their remote user authentication with the deprecated NTLM protocol. This could allow unauthenticated remote attackers, who have achieved a machine in the middle position, to relay NTLM authentication and impersonate a legitimate user. The potential impact depends on the services that are accessible, e.g. a SQL server used by WinCC.

## Affected and fixed versions

- Siemens SIMATIC BATCH V9.1: \< \* (cvelist)
- Siemens SIMATIC Information Server 2020: \< \* (cvelist)
- Siemens SIMATIC Information Server 2022: \< \* (cvelist)
- Siemens SIMATIC PCS 7 V9.1: \< \* (cvelist)
- Siemens SIMATIC Process Historian 2020: \< \* (cvelist)
- Siemens SIMATIC Process Historian 2022: \< \* (cvelist)
- Siemens SIMATIC WinCC Runtime Professional V17: \< \* (cvelist)
- Siemens SIMATIC WinCC Runtime Professional V18: \< \* (cvelist)
- Siemens SIMATIC WinCC Runtime Professional V19: \< \* (cvelist)
- Siemens SIMATIC WinCC Runtime Professional V20: \< \* (cvelist)
- Siemens SIMATIC WinCC Runtime Professional V21: \< \* (cvelist)
- Siemens SIMATIC WinCC V7.5: \< \* (cvelist)
- Siemens SIMATIC WinCC V8.0: \< \* (cvelist)
- Siemens SIMATIC WinCC V8.1: \< \* (cvelist)

## Mitigation

- No fix listed yet: follow the vendor advisory.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2026-58114. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2026-58114.md
Affected: Siemens SIMATIC BATCH V9.1 < *; Siemens SIMATIC Information Server 2020 < *; Siemens SIMATIC Information Server 2022 < *; Siemens SIMATIC PCS 7 V9.1 < *; Siemens SIMATIC Process Historian 2020 < *; Siemens SIMATIC Process Historian 2022 < *; Siemens SIMATIC WinCC Runtime Professional V17 < *; Sieme…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens SIMATIC BATCH V9.1, Siemens SIMATIC Information Server 2020, Siemens SIMATIC Information Server 2022, Siemens SIMATIC PCS 7 V9.1, Siemens SIMATIC Process Historian 2020, Siemens SIMATIC Process Historian 2022: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2026-58114 being exploited?

There is no confirmed exploitation: CVE-2026-58114 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.52% chance of exploitation in the next 30 days (as of 2026-11-28).

### How serious is CVE-2026-58114?

High: CVSS 7.7 (v4.0, scored by CNA). Remote, no login needed. A user has to take an action, such as opening a link, for the attack to work.

### Which versions are affected by CVE-2026-58114?

Siemens SIMATIC BATCH V9.1 \< \*; Siemens SIMATIC Information Server 2020 \< \*; Siemens SIMATIC Information Server 2022 \< \*; Siemens SIMATIC PCS 7 V9.1 \< \*; Siemens SIMATIC Process Historian 2020 \< \*; Siemens SIMATIC Process Historian 2022 \< \*; Siemens SIMATIC WinCC Runtime Professional V17 \< \*; Siemens SIMATIC WinCC Runtime Professional V18 \< \*; Siemens SIMATIC WinCC Runtime Professional V19 \< \*; Siemens SIMATIC WinCC Runtime Professional V20 \< \*; Siemens SIMATIC WinCC Runtime Professional V21 \< \*; Siemens SIMATIC WinCC V7.5 \< \*; Siemens SIMATIC WinCC V8.0 \< \*; Siemens SIMATIC WinCC V8.1 \< \*.

### Is there a fix for CVE-2026-58114?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

### How do I check if I'm affected by CVE-2026-58114?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- other: <https://cert-portal.siemens.com/productcert/html/ssa-970803.html>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2026-58114>
- FIRST EPSS: EPSS scores by FIRST <https://www.first.org/epss/>

HTML: <https://flawdb.com/CVE-2026-58114> · JSON: <https://flawdb.com/api/v1/entries/CVE-2026-58114>