Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2026-12818

CRITICAL 9.3EPSS 29%

DVP-12SE Exposure of Sensitive Information Vulnerability

Mitigation

  • Vendor workaround: Users are recommended to take the following mitigation measures:
  • * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access.
  • * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with.
  • * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.

Who should check

  • Anyone running deltaww DVP-12SE (versions: see the vendor advisory)

Vulnerability facts

Affected
deltaww DVP-12SE
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
9.3 (v4.0, CNA)CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Attack requirements: None
  • Privileges required: None
  • User interaction: None
  • Confidentiality impact: High
  • Integrity impact: High
  • Availability impact: High
  • Confidentiality impact on other systems: None
  • Integrity impact on other systems: None
  • Availability impact on other systems: None
EPSS
0.43% chance of exploitation in 30 days (percentile 29, 2026-11-26)
CWE
CWE-770
Published
Modified

Description

Delta Electronics DVP12SE PLCs are susceptible to a resource allocation vulnerability without limits or throttling (CWE-770) within their Modbus TCP service.

Affected and fixed versions

Package / productAffectedFixedSource
deltaww DVP-12SE——cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2026-12818. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2026-12818.md
Affected: deltaww DVP-12SE
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for deltaww DVP-12SE: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2026-12818 being exploited?

There is no confirmed exploitation: CVE-2026-12818 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.43% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2026-12818?

Critical: CVSS 9.3 (v4.0, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2026-12818?

deltaww DVP-12SE.

Is there a fix for CVE-2026-12818?

No fixed version is listed in the sources yet. Vendor workaround: Users are recommended to take the following mitigation measures: * Enable the IP Filter feature: Configure and enable the PLC's built-in IP Filter function via the programming software. Restrict access exclusively to the IP addresses of trusted devices (such as designated HMI panels or SCADA hosts) to block unauthorized network access. * Set up PLC password protection: Enable password protection for the PLC within the programming software to ensure the device's core control logic and parameters cannot be easily downloaded, overwritten, or tampered with. * Implement network isolation and firewall protection: Deploy the PLC within an independent local area network (OT control network) secured by a firewall. Never connect the device directly to the office network or the Internet. If remote access is required, enforce the use of a secure, authorized VPN tunnel.

How do I check if I'm affected by CVE-2026-12818?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors