CVE-2025-41738

HIGH 7.5EPSS 52%

CODESYS Control - Invalid type usage in visualization

Mitigation

  • Upgrade CODESYS Control RTE (SL) to 3.5.21.40 or later.
  • Upgrade CODESYS Control RTE (for Beckhoff CX) SL to 3.5.21.40 or later.
  • Upgrade CODESYS Control Win (SL) to 3.5.21.40 or later.
  • Upgrade CODESYS HMI (SL) to 3.5.21.40 or later.
  • Upgrade CODESYS Remote Target Visu to 3.5.21.40 or later.
  • Upgrade CODESYS Runtime Toolkit to 3.5.21.40 or later.
  • Upgrade CODESYS Control for BeagleBone SL to 4.19.0.0 or later.
  • Upgrade CODESYS Control for emPC-A/iMX6 SL to 4.19.0.0 or later.

Who should check

  • Anyone running CODESYS Control RTE (SL) >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS Control RTE (for Beckhoff CX) SL >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS Control Win (SL) >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS HMI (SL) >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS Remote Target Visu >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS Runtime Toolkit >= 3.5.18.0, < 3.5.21.40
  • Anyone running CODESYS Control for BeagleBone SL >= 4.5.0.0, < 4.19.0.0
  • Anyone running CODESYS Control for emPC-A/iMX6 SL >= 4.5.0.0, < 4.19.0.0

Vulnerability facts

Affected
CODESYS Control RTE (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.5.18.0, < 3.5.21.40; CODESYS Control Win (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS HMI (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Remote Target Visu >= 3.5.18.0, < 3.5.21.40; CODESYS Runtime Toolkit >= 3.5.18.0, < 3.5.21.40; CODESYS Control for BeagleBone SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for emPC-A/iMX6 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for IOT2000 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Linux ARM SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Linux SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PFC100 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PFC200 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PLCnext SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Raspberry Pi SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for WAGO Touch Panels 600 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Virtual Control SL >= 4.5.0.0, < 4.19.0.0
Fixed in
CODESYS Control RTE (SL) 3.5.21.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.21.40, CODESYS Control Win (SL) 3.5.21.40, CODESYS HMI (SL) 3.5.21.40, CODESYS Remote Target Visu 3.5.21.40, CODESYS Runtime Toolkit 3.5.21.40, CODESYS Control for BeagleBone SL 4.19.0.0, CODESYS Control for emPC-A/iMX6 SL 4.19.0.0, CODESYS Control for IOT2000 SL 4.19.0.0, CODESYS Control for Linux ARM SL 4.19.0.0, CODESYS Control for Linux SL 4.19.0.0, CODESYS Control for PFC100 SL 4.19.0.0, CODESYS Control for PFC200 SL 4.19.0.0, CODESYS Control for PLCnext SL 4.19.0.0, CODESYS Control for Raspberry Pi SL 4.19.0.0, CODESYS Control for WAGO Touch Panels 600 SL 4.19.0.0, CODESYS Virtual Control SL 4.19.0.0
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: None
  • User interaction: None
  • Scope: Unchanged
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: High
EPSS
0.77% chance of exploitation in 30 days (percentile 52, 2026-11-26)
CWE
CWE-843
Published
Modified

Description

An unauthenticated remote attacker may cause the visualisation server of the CODESYS Control runtime system to access a resource with a pointer of wrong type, potentially leading to a denial-of-service (DoS) condition.

Affected and fixed versions

Package / productAffectedFixedSource
CODESYS Control RTE (SL)>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS Control RTE (for Beckhoff CX) SL>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS Control Win (SL)>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS HMI (SL)>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS Remote Target Visu>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS Runtime Toolkit>= 3.5.18.0, < 3.5.21.40—cvelist
CODESYS Control for BeagleBone SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for emPC-A/iMX6 SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for IOT2000 SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for Linux ARM SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for Linux SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for PFC100 SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for PFC200 SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for PLCnext SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for Raspberry Pi SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Control for WAGO Touch Panels 600 SL>= 4.5.0.0, < 4.19.0.0—cvelist
CODESYS Virtual Control SL>= 4.5.0.0, < 4.19.0.0—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2025-41738. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2025-41738.md
Affected: CODESYS Control RTE (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.5.18.0, < 3.5.21.40; CODESYS Control Win (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS HMI (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Remote Target Visu >= 3.5.18.0, < 3.5.21.40; CODESYS Runtime Toolkit >= 3.5.18.…
Fixed in: CODESYS Control RTE (SL) 3.5.21.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.21.40, CODESYS Control Win (SL) 3.5.21.40, CODESYS HMI (SL) 3.5.21.40, CODESYS Remote Target Visu 3.5.21.40, CODESYS Runtime Toolkit 3.5.21.40, CODESYS Control for BeagleBone SL 4.19.0.0, CODESYS Control for emPC-A/iMX…

Steps:
1. Search this machine and project for CODESYS Control RTE (SL), CODESYS Control RTE (for Beckhoff CX) SL, CODESYS Control Win (SL), CODESYS HMI (SL), CODESYS Remote Target Visu, CODESYS Runtime Toolkit: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2025-41738 being exploited?

There is no confirmed exploitation: CVE-2025-41738 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.77% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2025-41738?

High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2025-41738?

CODESYS Control RTE (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Control RTE (for Beckhoff CX) SL >= 3.5.18.0, < 3.5.21.40; CODESYS Control Win (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS HMI (SL) >= 3.5.18.0, < 3.5.21.40; CODESYS Remote Target Visu >= 3.5.18.0, < 3.5.21.40; CODESYS Runtime Toolkit >= 3.5.18.0, < 3.5.21.40; CODESYS Control for BeagleBone SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for emPC-A/iMX6 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for IOT2000 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Linux ARM SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Linux SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PFC100 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PFC200 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for PLCnext SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for Raspberry Pi SL >= 4.5.0.0, < 4.19.0.0; CODESYS Control for WAGO Touch Panels 600 SL >= 4.5.0.0, < 4.19.0.0; CODESYS Virtual Control SL >= 4.5.0.0, < 4.19.0.0.

Is there a fix for CVE-2025-41738?

Yes. Fixed in CODESYS Control RTE (SL) 3.5.21.40, CODESYS Control RTE (for Beckhoff CX) SL 3.5.21.40, CODESYS Control Win (SL) 3.5.21.40, CODESYS HMI (SL) 3.5.21.40, CODESYS Remote Target Visu 3.5.21.40, CODESYS Runtime Toolkit 3.5.21.40, CODESYS Control for BeagleBone SL 4.19.0.0, CODESYS Control for emPC-A/iMX6 SL 4.19.0.0, CODESYS Control for IOT2000 SL 4.19.0.0, CODESYS Control for Linux ARM SL 4.19.0.0, CODESYS Control for Linux SL 4.19.0.0, CODESYS Control for PFC100 SL 4.19.0.0, CODESYS Control for PFC200 SL 4.19.0.0, CODESYS Control for PLCnext SL 4.19.0.0, CODESYS Control for Raspberry Pi SL 4.19.0.0, CODESYS Control for WAGO Touch Panels 600 SL 4.19.0.0, CODESYS Virtual Control SL 4.19.0.0. Upgrade CODESYS Control RTE (SL) to 3.5.21.40 or later. Upgrade CODESYS Control RTE (for Beckhoff CX) SL to 3.5.21.40 or later. Upgrade CODESYS Control Win (SL) to 3.5.21.40 or later. Upgrade CODESYS HMI (SL) to 3.5.21.40 or later. Upgrade CODESYS Remote Target Visu to 3.5.21.40 or later. Upgrade CODESYS Runtime Toolkit to 3.5.21.40 or later. Upgrade CODESYS Control for BeagleBone SL to 4.19.0.0 or later. Upgrade CODESYS Control for emPC-A/iMX6 SL to 4.19.0.0 or later.

How do I check if I'm affected by CVE-2025-41738?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors