# CVE-2025-40944: A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200…

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** HIGH 8.7
- **CVSS:** 8.7 (v4.0, CNA) `CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Attack requirements: None; Privileges required: None; User interaction: None; Confidentiality impact: None; Integrity impact: None; Availability impact: High; Confidentiality impact on other systems: None; Integrity impact on other systems: None; Availability impact on other systems: None
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 0.57% (percentile 41, 2026-11-26)
- **CWE:** CWE-400
- **Published:** 2026-01-13T09:44:05.792Z
- **Modified:** 2026-06-17T09:22:20.997Z

## Who should check

- Anyone running Siemens SIMATIC ET 200AL IM 157-1 PN \< \*
- Anyone running Siemens SIMATIC ET 200MP IM 155-5 PN HF \>= V4.2.0, \< \*
- Anyone running Siemens SIMATIC ET 200SP IM 155-6 MF HF \< \*
- Anyone running Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) \< V1.3
- Anyone running Siemens SIMATIC ET 200SP IM 155-6 PN R1 \< V6.0.1
- Anyone running Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF \>= V4.2.0, \< V4.2.5
- Anyone running Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF \< V4.2.2
- Anyone running Siemens SIMATIC PN/MF Coupler \< \*

## Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions \>= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions \< V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions \< V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions \>= V4.2.0 \< V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions \< V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions \< V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions \>= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions \>= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions \>= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions \>= V4.2.0 \< V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions \>= V4.2.0 \< V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions \>= V4.2.0 \< V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions \>= V4.2.0 \< V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions \< V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state.

This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

## Affected and fixed versions

- Siemens SIMATIC ET 200AL IM 157-1 PN: \< \* (cvelist)
- Siemens SIMATIC ET 200MP IM 155-5 PN HF: \>= V4.2.0, \< \* (cvelist)
- Siemens SIMATIC ET 200SP IM 155-6 MF HF: \< \* (cvelist)
- Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants): \< V1.3 (cvelist)
- Siemens SIMATIC ET 200SP IM 155-6 PN R1: \< V6.0.1 (cvelist)
- Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF: \>= V4.2.0, \< V4.2.5 (cvelist)
- Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF: \< V4.2.2 (cvelist)
- Siemens SIMATIC PN/MF Coupler: \< \* (cvelist)
- Siemens SIMATIC PN/PN Coupler: \< V6.0.0 (cvelist)
- Siemens SIPLUS ET 200MP IM 155-5 PN HF: \>= V4.2.0, \< \* (cvelist)
- Siemens SIPLUS ET 200MP IM 155-5 PN HF: \>= V4.2.0, \< \* (cvelist)
- Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL: \>= V4.2.0, \< \* (cvelist)
- Siemens SIPLUS ET 200SP IM 155-6 PN HF: \>= V4.2.0, \< V4.2.5 (cvelist)
- Siemens SIPLUS ET 200SP IM 155-6 PN HF: \>= V4.2.0, \< V4.2.5 (cvelist)
- Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL: \>= V4.2.0, \< V4.2.5 (cvelist)
- Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL: \>= V4.2.0, \< V4.2.5 (cvelist)
- Siemens SIPLUS NET PN/PN Coupler: \< V6.0.0 (cvelist)

## Mitigation

- No fix listed yet: follow the vendor advisory.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2025-40944. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2025-40944.md
Affected: Siemens SIMATIC ET 200AL IM 157-1 PN < *; Siemens SIMATIC ET 200MP IM 155-5 PN HF >= V4.2.0, < *; Siemens SIMATIC ET 200SP IM 155-6 MF HF < *; Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) < V1.3; Siemens SIMATIC ET 200SP IM 155-6 PN R1 < V6.0.1; Siemens SIMATIC ET 200SP IM 155-6 …
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens SIMATIC ET 200AL IM 157-1 PN, Siemens SIMATIC ET 200MP IM 155-5 PN HF, Siemens SIMATIC ET 200SP IM 155-6 MF HF, Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants), Siemens SIMATIC ET 200SP IM 155-6 PN R1, Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2025-40944 being exploited?

There is no confirmed exploitation: CVE-2025-40944 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.57% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2025-40944?

High: CVSS 8.7 (v4.0, scored by CNA). Remote, no login needed.

### Which versions are affected by CVE-2025-40944?

Siemens SIMATIC ET 200AL IM 157-1 PN \< \*; Siemens SIMATIC ET 200MP IM 155-5 PN HF \>= V4.2.0, \< \*; Siemens SIMATIC ET 200SP IM 155-6 MF HF \< \*; Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) \< V1.3; Siemens SIMATIC ET 200SP IM 155-6 PN R1 \< V6.0.1; Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF \>= V4.2.0, \< V4.2.5; Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF \< V4.2.2; Siemens SIMATIC PN/MF Coupler \< \*; Siemens SIMATIC PN/PN Coupler \< V6.0.0; Siemens SIPLUS ET 200MP IM 155-5 PN HF \>= V4.2.0, \< \*; Siemens SIPLUS ET 200MP IM 155-5 PN HF \>= V4.2.0, \< \*; Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL \>= V4.2.0, \< \*; Siemens SIPLUS ET 200SP IM 155-6 PN HF \>= V4.2.0, \< V4.2.5; Siemens SIPLUS ET 200SP IM 155-6 PN HF \>= V4.2.0, \< V4.2.5; Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL \>= V4.2.0, \< V4.2.5; Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL \>= V4.2.0, \< V4.2.5; Siemens SIPLUS NET PN/PN Coupler \< V6.0.0.

### Is there a fix for CVE-2025-40944?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

### How do I check if I'm affected by CVE-2025-40944?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- other: <https://cert-portal.siemens.com/productcert/html/ssa-674753.html>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2025-40944>

HTML: <https://flawdb.com/CVE-2025-40944> · JSON: <https://flawdb.com/api/v1/entries/CVE-2025-40944>