CVE-2025-3756
Denial of Service Vulnerabilities in System 800xA, Symphony® Plus IEC 61850
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running ABB AC800M (System 800xA) >= 6.0.0x, <= 6.0.0303.0; >= 6.1.0x, <= 6.1.0031.0; >= 6.1.1x, <= 6.1.1004.0; >= 6.1.1x, <= 6.1.1202.0; >= 6.2.0x, <= 6.2.0006.0
- Anyone running ABB Symphony Plus SD Series A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005
- Anyone running ABB Symphony Plus MR (Melody Rack) >= 3.10, <= 3.52
- Anyone running ABB S+ Operations 2.1; 2.2; 2.3; 3.3
Vulnerability facts
- Affected
- ABB AC800M (System 800xA) >= 6.0.0x, <= 6.0.0303.0; >= 6.1.0x, <= 6.1.0031.0; >= 6.1.1x, <= 6.1.1004.0; >= 6.1.1x, <= 6.1.1202.0; >= 6.2.0x, <= 6.2.0006.0; ABB Symphony Plus SD Series A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005; ABB Symphony Plus MR (Melody Rack) >= 3.10, <= 3.52; ABB S+ Operations 2.1; 2.2; 2.3; 3.3
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 7.1 (v4.0, CNA)CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
- Attack vector: Adjacent network
- Attack complexity: Low
- Attack requirements: None
- Privileges required: None
- User interaction: None
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: High
- Confidentiality impact on other systems: None
- Integrity impact on other systems: None
- Availability impact on other systems: None
- EPSS
- 0.28% chance of exploitation in 30 days (percentile 13, 2026-11-26)
- CWE
- CWE-1284
- Modified
Description
A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation. The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function. This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| ABB AC800M (System 800xA) | >= 6.0.0x, <= 6.0.0303.0; >= 6.1.0x, <= 6.1.0031.0; >= 6.1.1x, <= 6.1.1004.0; >= 6.1.1x, <= 6.1.1202.0; >= 6.2.0x, <= 6.2.0006.0 | — | cvelist |
| ABB Symphony Plus SD Series | A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005 | — | cvelist |
| ABB Symphony Plus MR (Melody Rack) | >= 3.10, <= 3.52 | — | cvelist |
| ABB S+ Operations | 2.1; 2.2; 2.3; 3.3 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2025-3756. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2025-3756.md Affected: ABB AC800M (System 800xA) >= 6.0.0x, <= 6.0.0303.0; >= 6.1.0x, <= 6.1.0031.0; >= 6.1.1x, <= 6.1.1004.0; >= 6.1.1x, <= 6.1.1202.0; >= 6.2.0x, <= 6.2.0006.0; ABB Symphony Plus SD Series A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005; ABB Symphony Plus MR (Melody Rack) >= 3.10, <= 3.52; ABB S+ Operation… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for ABB AC800M (System 800xA), ABB Symphony Plus SD Series, ABB Symphony Plus MR (Melody Rack), ABB S+ Operations: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2025-3756 being exploited?
There is no confirmed exploitation: CVE-2025-3756 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.28% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2025-3756?
High: CVSS 7.1 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed).
Which versions are affected by CVE-2025-3756?
ABB AC800M (System 800xA) >= 6.0.0x, <= 6.0.0303.0; >= 6.1.0x, <= 6.1.0031.0; >= 6.1.1x, <= 6.1.1004.0; >= 6.1.1x, <= 6.1.1202.0; >= 6.2.0x, <= 6.2.0006.0; ABB Symphony Plus SD Series A_0; A_1; A_2.003; A_3.005; A_4.001; B_0.005; ABB Symphony Plus MR (Melody Rack) >= 3.10, <= 3.52; ABB S+ Operations 2.1; 2.2; 2.3; 3.3.
Is there a fix for CVE-2025-3756?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2025-3756?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.