Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2025-24482

HIGH 7.0EPSS 25%

FactoryTalk® View Site Edition - Local Code Injection

Mitigation

  • Vendor workaround: Check the environment variables (PATH), and make sure FactoryTalk® View SE installation path (C:\Program Files (x86)\Common Files\Rockwell) is before all others

Who should check

  • Anyone running Rockwell Automation FactoryTalk® View Site Edition <V15

Vulnerability facts

Affected
Rockwell Automation FactoryTalk® View Site Edition <V15
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Not remotely exploitable (local or adjacent access needed)
CVSS
7.0 (v4.0, CNA)CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:L/VI:L/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
  • Attack vector: Local
  • Attack complexity: Low
  • Attack requirements: None
  • Privileges required: None
  • User interaction: None
  • Confidentiality impact: Low
  • Integrity impact: Low
  • Availability impact: High
  • Confidentiality impact on other systems: None
  • Integrity impact on other systems: None
  • Availability impact on other systems: None
EPSS
0.40% chance of exploitation in 30 days (percentile 25, 2026-11-26)
CWE
CWE-94
Published
Modified

Description

A Local Code Injection Vulnerability exists in the product and version listed above. The vulnerability is due to incorrect default permissions and allows for DLLs to be executed with higher level permissions.

Affected and fixed versions

Package / productAffectedFixedSource
Rockwell Automation FactoryTalk® View Site Edition<V15—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2025-24482. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2025-24482.md
Affected: Rockwell Automation FactoryTalk® View Site Edition <V15
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Rockwell Automation FactoryTalk® View Site Edition: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2025-24482 being exploited?

There is no confirmed exploitation: CVE-2025-24482 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.40% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2025-24482?

High: CVSS 7.0 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed).

Which versions are affected by CVE-2025-24482?

Rockwell Automation FactoryTalk® View Site Edition <V15.

Is there a fix for CVE-2025-24482?

No fixed version is listed in the sources yet. Vendor workaround: Check the environment variables (PATH), and make sure FactoryTalk® View SE installation path (C:\Program Files (x86)\Common Files\Rockwell) is before all others

How do I check if I'm affected by CVE-2025-24482?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors