Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2025-13911

HIGH 7.3EPSS 23%

Inductive Automation Ignition Execution with Unnecessary Privileges

Mitigation

  • Vendor workaround: Inductive Automation encourages users to do the following in order to reduce the risk of this vulnerability:
  • * Create a new dedicated local Windows account that will be used
  • exclusively for the Ignition service (e.g. svc-ign) (this should not be a
  • domain account).
  • *
  • Remove all group memberships from the service account (including Users and Administrators).
  • * Add to security policy to log in as a service.
  • * Add to “Deny log on locally” security policy.
  • *
  • Provide full read/write access only to the Ignition installation directory for the service account created in step 1.
  • *
  • Add read/write permissions to other directories in the local filesystem
  • as needed (e.g: if configured to use optional Enterprise Administration
  • Module to write automated backups to the file system).
  • *
  • Set deny access settings for service account on other directories not needed by the Ignition service.
  • *
  • Specifically the C:\Windows, C:\Users, and directories for any other
  • applications in the Program Files or Program Files (x86) directories.
  • *
  • Use java param to change temp directory to a location within the
  • Ignition install directory so the Users folder can be denied access to
  • the Ignition service account.
  • *
  • Restrict project imports to verified and trusted sources only, ideally using checksums or digital signatures.
  • *
  • Use multiple environments (e.g. Dev, Test, Prod) with a staging workflow
  • so that new data is never introduced directly to Production
  • environments. See Ignition Deployment Best Practices.
  • *
  • When feasible, segment or isolate Ignition gateways from corporate resources and Windows Domains.
  • *
  • The Ignition service account or AD server object should never need
  • Windows Domain or Windows Active Directory privileges. This would only
  • be needed if an Asset Owners IT or OT department uses this for
  • management outside Ignition.
  • *
  • Ignition may be federated with Active Directory environments (e.g. OT
  • domains) by entering “Authentication Profile” credentials within the
  • Ignition gateway itself. This could use secure LDAP, SAML, or OpenID
  • Connect.
  • *
  • When feasible, enforce strong credential management and MFA for all
  • users with Designer permissions (8.1.x and 8.3.x), Config Page
  • permissions (8.1.x), and Config Write permissions (8.3.x).
  • *
  • When feasible, deploy Ignition within hardened or containerized environments.

Who should check

  • Anyone running Inductive Automation Ignition 8.1.x; 8.3.x

Vulnerability facts

Affected
Inductive Automation Ignition 8.1.x; 8.3.x
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Not remotely exploitable (local or adjacent access needed)
CVSS
7.3 (v4.0, CNA)CVSS:4.0/AV:A/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
  • Attack vector: Adjacent network
  • Attack complexity: High
  • Attack requirements: None
  • Privileges required: High
  • User interaction: None
  • Confidentiality impact: High
  • Integrity impact: High
  • Availability impact: High
  • Confidentiality impact on other systems: None
  • Integrity impact on other systems: None
  • Availability impact on other systems: None
EPSS
0.37% chance of exploitation in 30 days (percentile 23, 2026-11-26)
CWE
CWE-250
Published
Modified

Description

Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations. On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.

Affected and fixed versions

Package / productAffectedFixedSource
Inductive Automation Ignition8.1.x; 8.3.x—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2025-13911. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2025-13911.md
Affected: Inductive Automation Ignition 8.1.x; 8.3.x
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Inductive Automation Ignition: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2025-13911 being exploited?

There is no confirmed exploitation: CVE-2025-13911 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.37% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2025-13911?

High: CVSS 7.3 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed). The attack needs conditions outside the attacker's control, which makes it harder.

Which versions are affected by CVE-2025-13911?

Inductive Automation Ignition 8.1.x; 8.3.x.

Is there a fix for CVE-2025-13911?

No fixed version is listed in the sources yet. Vendor workaround: Inductive Automation encourages users to do the following in order to reduce the risk of this vulnerability: * Create a new dedicated local Windows account that will be used exclusively for the Ignition service (e.g. svc-ign) (this should not be a domain account). * Remove all group memberships from the service account (including Users and Administrators). * Add to security policy to log in as a service. * Add to “Deny log on locally” security policy. * Provide full read/write access only to the Ignition installation directory for the service account created in step 1. * Add read/write permissions to other directories in the local filesystem as needed (e.g: if configured to use optional Enterprise Administration Module to write automated backups to the file system). * Set deny access settings for service account on other directories not needed by the Ignition service. * Specifically the C:\Windows, C:\Users, and directories for any other applications in the Program Files or Program Files (x86) directories. * Use java param to change temp directory to a location within the Ignition install directory so the Users folder can be denied access to the Ignition service account. * Restrict project imports to verified and trusted sources only, ideally using checksums or digital signatures. * Use multiple environments (e.g. Dev, Test, Prod) with a staging workflow so that new data is never introduced directly to Production environments. See Ignition Deployment Best Practices. * When feasible, segment or isolate Ignition gateways from corporate resources and Windows Domains. * The Ignition service account or AD server object should never need Windows Domain or Windows Active Directory privileges. This would only be needed if an Asset Owners IT or OT department uses this for management outside Ignition. * Ignition may be federated with Active Directory environments (e.g. OT domains) by entering “Authentication Profile” credentials within the Ignition gateway itself. This could use secure LDAP, SAML, or OpenID Connect. * When feasible, enforce strong credential management and MFA for all users with Designer permissions (8.1.x and 8.3.x), Config Page permissions (8.1.x), and Config Write permissions (8.3.x). * When feasible, deploy Ignition within hardened or containerized environments.

How do I check if I'm affected by CVE-2025-13911?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors