CVE-2024-6242
Rockwell Automation Chassis Restrictions Bypass Vulnerability in Select Logix Devices
Mitigation
- Vendor workaround: Affected Product
- First Known in Firmware Revision
- Corrected in Firmware Revision
- ControlLogix® 5580 (1756-L8z)
- V28
- V32.016, V33.015, V34.014,
- V35.011 and later
- GuardLogix® 5580 (1756-L8zS)
- V31
- V32.016, V33.015, V34.014,
- V35.011 and later
- 1756-EN4TR
- V2
- V5.001 and later
- 1756-EN2T, Series A/B/C
- 1756-EN2F, Series A/B
- 1756-EN2TR, Series A/B
- 1756-EN3TR, Series B
- v5.007(unsigned)/v5.027(signed)
- No fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability
- 1756-EN2T, Series D
- 1756-EN2F, Series C
- 1756-EN2TR, Series C
- 1756-EN3TR, Series B
- 1756-EN2TP, Series A
- 1756-EN2T/D: V10.006
- 1756-EN2F/C: V10.009
- 1756-EN2TR/C: V10.007
- 1756-EN3TR/B: V10.007
- 1756-EN2TP/A: V10.020
- V12.001 and later
- Users using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible.
- * Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position.
- * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
Who should check
- Anyone running Rockwell Automation ControlLogix® 5580 (1756-L8z) V28
- Anyone running Rockwell Automation GuardLogix® 5580 (1756-L8zS) V31
- Anyone running Rockwell Automation 1756-EN4TR V2
- Anyone running Rockwell Automation 1756-EN2T v5.007(unsigned)/v5.027(signed)
- Anyone running Rockwell Automation 1756-EN2F v5.007(unsigned)/v5.027(signed)
- Anyone running Rockwell Automation 1756-EN2TR v5.007(unsigned)/v5.027(signed)
- Anyone running Rockwell Automation 1756-EN3TR v5.007(unsigned)/v5.027(signed)
- Anyone running Rockwell Automation 1756-EN2T 1756-EN2T/D: V10.006
Vulnerability facts
- Affected
- Rockwell Automation ControlLogix® 5580 (1756-L8z) V28; Rockwell Automation GuardLogix® 5580 (1756-L8zS) V31; Rockwell Automation 1756-EN4TR V2; Rockwell Automation 1756-EN2T v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2F v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2TR v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN3TR v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2T 1756-EN2T/D: V10.006; Rockwell Automation 1756-EN2F 1756-EN2F/C: V10.009; Rockwell Automation 1756-EN2TR 1756-EN2TR/C: V10.007; Rockwell Automation 1756-EN3TR 1756-EN3TR/B: V10.007; Rockwell Automation 1756-EN2TP 1756-EN2TP/A: V10.020
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, login needed
- CVSS
- 7.3 (v4.0, CNA)CVSS:4.0/AV:N/AC:L/AT:P/PR:L/UI:N/VC:L/VI:H/VA:H/SC:L/SI:H/SA:HOpen in CVSS calculator
Show all 11 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Attack requirements: Present
- Privileges required: Low
- User interaction: None
- Confidentiality impact: Low
- Integrity impact: High
- Availability impact: High
- Confidentiality impact on other systems: Low
- Integrity impact on other systems: High
- Availability impact on other systems: High
- EPSS
- 0.67% chance of exploitation in 30 days (percentile 47, 2026-11-26)
- CWE
- CWE-420
- Modified
Description
A vulnerability exists in Rockwell Automation affected products that allows a threat actor to bypass the Trusted® Slot feature in a ControlLogix® controller. If exploited on any affected module in a 1756 chassis, a threat actor could potentially execute CIP commands that modify user projects and/or device configuration on a Logix controller in the chassis.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Rockwell Automation ControlLogix® 5580 (1756-L8z) | V28 | — | cvelist |
| Rockwell Automation GuardLogix® 5580 (1756-L8zS) | V31 | — | cvelist |
| Rockwell Automation 1756-EN4TR | V2 | — | cvelist |
| Rockwell Automation 1756-EN2T | v5.007(unsigned)/v5.027(signed) | — | cvelist |
| Rockwell Automation 1756-EN2F | v5.007(unsigned)/v5.027(signed) | — | cvelist |
| Rockwell Automation 1756-EN2TR | v5.007(unsigned)/v5.027(signed) | — | cvelist |
| Rockwell Automation 1756-EN3TR | v5.007(unsigned)/v5.027(signed) | — | cvelist |
| Rockwell Automation 1756-EN2T | 1756-EN2T/D: V10.006 | — | cvelist |
| Rockwell Automation 1756-EN2F | 1756-EN2F/C: V10.009 | — | cvelist |
| Rockwell Automation 1756-EN2TR | 1756-EN2TR/C: V10.007 | — | cvelist |
| Rockwell Automation 1756-EN3TR | 1756-EN3TR/B: V10.007 | — | cvelist |
| Rockwell Automation 1756-EN2TP | 1756-EN2TP/A: V10.020 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2024-6242. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2024-6242.md Affected: Rockwell Automation ControlLogix® 5580 (1756-L8z) V28; Rockwell Automation GuardLogix® 5580 (1756-L8zS) V31; Rockwell Automation 1756-EN4TR V2; Rockwell Automation 1756-EN2T v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2F v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2T… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Rockwell Automation ControlLogix® 5580 (1756-L8z), Rockwell Automation GuardLogix® 5580 (1756-L8zS), Rockwell Automation 1756-EN4TR, Rockwell Automation 1756-EN2T, Rockwell Automation 1756-EN2F, Rockwell Automation 1756-EN2TR: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2024-6242 being exploited?
There is no confirmed exploitation: CVE-2024-6242 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.67% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2024-6242?
High: CVSS 7.3 (v4.0, scored by CNA). Remote, login needed.
Which versions are affected by CVE-2024-6242?
Rockwell Automation ControlLogix® 5580 (1756-L8z) V28; Rockwell Automation GuardLogix® 5580 (1756-L8zS) V31; Rockwell Automation 1756-EN4TR V2; Rockwell Automation 1756-EN2T v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2F v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2TR v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN3TR v5.007(unsigned)/v5.027(signed); Rockwell Automation 1756-EN2T 1756-EN2T/D: V10.006; Rockwell Automation 1756-EN2F 1756-EN2F/C: V10.009; Rockwell Automation 1756-EN2TR 1756-EN2TR/C: V10.007; Rockwell Automation 1756-EN3TR 1756-EN3TR/B: V10.007; Rockwell Automation 1756-EN2TP 1756-EN2TP/A: V10.020.
Is there a fix for CVE-2024-6242?
No fixed version is listed in the sources yet. Vendor workaround: Affected Product First Known in Firmware Revision Corrected in Firmware Revision ControlLogix® 5580 (1756-L8z) V28 V32.016, V33.015, V34.014, V35.011 and later GuardLogix® 5580 (1756-L8zS) V31 V32.016, V33.015, V34.014, V35.011 and later 1756-EN4TR V2 V5.001 and later 1756-EN2T, Series A/B/C 1756-EN2F, Series A/B 1756-EN2TR, Series A/B 1756-EN3TR, Series B v5.007(unsigned)/v5.027(signed) No fix is available for Series A/B/C. Users can upgrade to Series D to remediate this vulnerability 1756-EN2T, Series D 1756-EN2F, Series C 1756-EN2TR, Series C 1756-EN3TR, Series B 1756-EN2TP, Series A 1756-EN2T/D: V10.006 1756-EN2F/C: V10.009 1756-EN2TR/C: V10.007 1756-EN3TR/B: V10.007 1756-EN2TP/A: V10.020 V12.001 and later Users using the affected firmware and who are not able to upgrade to one of the corrected versions are encouraged to apply the following mitigation and security best practices, where possible. * Limit the allowed CIP commands on controllers by setting the mode switch to the RUN position. * Security Best Practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight
How do I check if I'm affected by CVE-2024-6242?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.