# CVE-2024-43099: AutomationDirect DirectLogic H2-DM1E Authentication Bypass by Capture-replay

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** HIGH 8.7
- **CVSS:** 8.7 (v4.0, CNA) `CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N`
- **CVSS metrics:** Attack vector: Adjacent network; Attack complexity: Low; Attack requirements: None; Privileges required: None; User interaction: None; Confidentiality impact: High; Integrity impact: High; Availability impact: High; Confidentiality impact on other systems: None; Integrity impact on other systems: None; Availability impact on other systems: None
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Not remotely exploitable (local or adjacent access needed)
- **EPSS:** 0.44% (percentile 30, 2026-11-26)
- **CWE:** CWE-294
- **Published:** 2024-09-13T16:33:02.575Z
- **Modified:** 2026-06-17T07:50:26.350Z

## Who should check

- Anyone running AutomationDirect DirectLogic H2-DM1E \<= 2.8.0

## Description

The session hijacking attack targets the application layer's control mechanism, which manages authenticated sessions between a host PC and a PLC. During such sessions, a session key is utilized to maintain security. However, if an attacker captures this session key, they can inject traffic into an ongoing authenticated session. To successfully achieve this, the attacker also needs to spoof both the IP address and MAC address of the originating host which is typical of a session-based attack.

## Affected and fixed versions

- AutomationDirect DirectLogic H2-DM1E: \<= 2.8.0 (cvelist)

## Mitigation

- Vendor workaround: As part of their ongoing risk assessment, AutomationDirect has determined that the H2-DM1E, due to its age and inherent architectural limitations, can no longer be supported within the secure development lifecycle.
- 
- To address these challenges, AutomationDirect recommends the following mitigation strategies based on a thorough risk assessment:
- 
-   \*  Upgrade to the BRX platform: Transitioning to the BRX platform is strongly advised, as it is designed to meet current security standards and is actively maintained within AutomationDirect's secure development lifecycle.
-   \*  Network segmentation and air gapping: To mitigate risks associated with the H2-DM1E, AutomationDirect recommends implementing network segmentation and air gapping. This strategy will isolate the older technology from the broader network, reducing its exposure to external threats and minimizing the impact of any security vulnerabilities.
-   \*  Deploy a StrideLinx secure VPN platform: AutomationDirect also recommends placing the system behind a StrideLinx VPN platform.
- 
- 
- These mitigation strategies provide a comprehensive approach to managing the risks associated with the H2-DM1E while preparing for future security needs.  Please reach out to AutomationDirect https://www.automationdirect.com/adc/contactus/contactus  if you have any further questions or require additional details on these recommendations.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2024-43099. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2024-43099.md
Affected: AutomationDirect DirectLogic H2-DM1E <= 2.8.0
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for AutomationDirect DirectLogic H2-DM1E: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2024-43099 being exploited?

There is no confirmed exploitation: CVE-2024-43099 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.44% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2024-43099?

High: CVSS 8.7 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed).

### Which versions are affected by CVE-2024-43099?

AutomationDirect DirectLogic H2-DM1E \<= 2.8.0.

### Is there a fix for CVE-2024-43099?

No fixed version is listed in the sources yet. Vendor workaround: As part of their ongoing risk assessment, AutomationDirect has determined that the H2-DM1E, due to its age and inherent architectural limitations, can no longer be supported within the secure development lifecycle.  To address these challenges, AutomationDirect recommends the following mitigation strategies based on a thorough risk assessment:    \*  Upgrade to the BRX platform: Transitioning to the BRX platform is strongly advised, as it is designed to meet current security standards and is actively maintained within AutomationDirect's secure development lifecycle.   \*  Network segmentation and air gapping: To mitigate risks associated with the H2-DM1E, AutomationDirect recommends implementing network segmentation and air gapping. This strategy will isolate the older technology from the broader network, reducing its exposure to external threats and minimizing the impact of any security vulnerabilities.   \*  Deploy a StrideLinx secure VPN platform: AutomationDirect also recommends placing the system behind a StrideLinx VPN platform.   These mitigation strategies provide a comprehensive approach to managing the risks associated with the H2-DM1E while preparing for future security needs.  Please reach out to AutomationDirect https://www.automationdirect.com/adc/contactus/contactus  if you have any further questions or require additional details on these recommendations.

### How do I check if I'm affected by CVE-2024-43099?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- other: <https://www.cisa.gov/news-events/ics-advisories/icsa-24-256-17>