CVE-2024-37365
FactoryTalk View ME Remote Code Execution Vulnerability via Project Save Path
Mitigation
- Vendor workaround: ·
- To enhance security and
- prevent unauthorized modifications to HMI project files, harden the Windows OS
- by removing the INTERACTIVE group from the folder’s
- security properties.
- ·
- Add specific users or user
- groups and assign their permissions to this folder using the least privileges
- principle. Users with read-only permission can still test run and run the
- FactoryTalk View ME Station.
- ·
- Guidance can be found in
- FactoryTalk View ME v14 Help topic: “HMI projects folder settings”. It can be opened through
- FactoryTalk View ME Studio menu “help\Contents\FactoryTalk View ME Help\Create
- a Machine Edition application->Open applications->HMI project folder settings”. Security
- Best Practices
Who should check
- Anyone running Rockwell Automation FactoryTalk View Machine Edition >=V14
Vulnerability facts
- Affected
- Rockwell Automation FactoryTalk View Machine Edition >=V14
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 7.0 (v4.0, CNA)CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:NOpen in CVSS calculator
Show all 11 CVSS metrics
- Attack vector: Local
- Attack complexity: Low
- Attack requirements: None
- Privileges required: Low
- User interaction: Passive
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- Confidentiality impact on other systems: None
- Integrity impact on other systems: None
- Availability impact on other systems: None
- EPSS
- 0.36% chance of exploitation in 30 days (percentile 22, 2026-11-26)
- CWE
- CWE-20
- Modified
Description
A remote code execution vulnerability exists in the affected product. The vulnerability allows users to save projects within the public directory allowing anyone with local access to modify and/or delete files. Additionally, a malicious user could potentially leverage this vulnerability to escalate their privileges by changing the macro to execute arbitrary code.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Rockwell Automation FactoryTalk View Machine Edition | >=V14 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2024-37365. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2024-37365.md Affected: Rockwell Automation FactoryTalk View Machine Edition >=V14 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Rockwell Automation FactoryTalk View Machine Edition: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2024-37365 being exploited?
There is no confirmed exploitation: CVE-2024-37365 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.36% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2024-37365?
High: CVSS 7.0 (v4.0, scored by CNA). Not remotely exploitable (local or adjacent access needed). A user has to take an action, such as opening a link, for the attack to work.
Which versions are affected by CVE-2024-37365?
Rockwell Automation FactoryTalk View Machine Edition >=V14.
Is there a fix for CVE-2024-37365?
No fixed version is listed in the sources yet. Vendor workaround: · To enhance security and prevent unauthorized modifications to HMI project files, harden the Windows OS by removing the INTERACTIVE group from the folder’s security properties. · Add specific users or user groups and assign their permissions to this folder using the least privileges principle. Users with read-only permission can still test run and run the FactoryTalk View ME Station. · Guidance can be found in FactoryTalk View ME v14 Help topic: “HMI projects folder settings”. It can be opened through FactoryTalk View ME Studio menu “help\Contents\FactoryTalk View ME Help\Create a Machine Edition application->Open applications->HMI project folder settings”. Security Best Practices
How do I check if I'm affected by CVE-2024-37365?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.