Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2023-51440

HIGH 7.5EPSS 59%

A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK…

Mitigation

  • No fix listed yet: follow the vendor advisory.

Who should check

  • Anyone running Siemens SIMATIC CP 343-1 All versions
  • Anyone running Siemens SIMATIC CP 343-1 Lean All versions
  • Anyone running Siemens SIPLUS NET CP 343-1 All versions
  • Anyone running Siemens SIPLUS NET CP 343-1 Lean All versions

Vulnerability facts

Affected
Siemens SIMATIC CP 343-1 All versions; Siemens SIMATIC CP 343-1 Lean All versions; Siemens SIPLUS NET CP 343-1 All versions; Siemens SIPLUS NET CP 343-1 Lean All versions
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H/E:P/RL:T/RC:COpen in CVSS calculator
Show all 11 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: None
  • User interaction: None
  • Scope: Unchanged
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: High
  • E: P
  • RL: T
  • RC: C
EPSS
0.92% chance of exploitation in 30 days (percentile 59, 2026-11-26)
CWE
CWE-940
Published
Modified

Description

A vulnerability has been identified in SIMATIC CP 343-1 (6GK7343-1EX30-0XE0) (All versions), SIMATIC CP 343-1 Lean (6GK7343-1CX10-0XE0) (All versions), SIPLUS NET CP 343-1 (6AG1343-1EX30-7XE0) (All versions), SIPLUS NET CP 343-1 Lean (6AG1343-1CX10-2XE0) (All versions). Affected products incorrectly validate TCP sequence numbers. This could allow an unauthenticated remote attacker to create a denial of service condition by injecting spoofed TCP RST packets.

Affected and fixed versions

Package / productAffectedFixedSource
Siemens SIMATIC CP 343-1All versions—cvelist
Siemens SIMATIC CP 343-1 LeanAll versions—cvelist
Siemens SIPLUS NET CP 343-1All versions—cvelist
Siemens SIPLUS NET CP 343-1 LeanAll versions—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2023-51440. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2023-51440.md
Affected: Siemens SIMATIC CP 343-1 All versions; Siemens SIMATIC CP 343-1 Lean All versions; Siemens SIPLUS NET CP 343-1 All versions; Siemens SIPLUS NET CP 343-1 Lean All versions
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens SIMATIC CP 343-1, Siemens SIMATIC CP 343-1 Lean, Siemens SIPLUS NET CP 343-1, Siemens SIPLUS NET CP 343-1 Lean: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2023-51440 being exploited?

There is no confirmed exploitation: CVE-2023-51440 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.92% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2023-51440?

High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2023-51440?

Siemens SIMATIC CP 343-1 All versions; Siemens SIMATIC CP 343-1 Lean All versions; Siemens SIPLUS NET CP 343-1 All versions; Siemens SIPLUS NET CP 343-1 Lean All versions.

Is there a fix for CVE-2023-51440?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.