CVE-2023-3322
Code Execution through overwriting service executable in utilities directory
Mitigation
- Vendor workaround: ABB recommends the following workarounds. Although these workarounds will not correct the underlying vulnerability, they block the known attack vectors.
- • For CVE-2023-3322, Recommended practices include that process control systems are physically protected,
- have no direct connections to the Internet, and are separated from other networks by
- means of a firewall system that has a minimal number of ports exposed. Remove the default directory permissions for ‘Everyone’ on the service grid, ABB utilities, and zenon_Projects directories and provide access only to specific users that are
- expected to access zenon. Install the IIoT services, which is, the Service grid component on a separate system. Secure the ZEE600 related executable files in ‘C:\ProgramData\ABB\ABBUtilities’ directory by removing the group named “Everyone”. Ensure the group name “Everyone” should be removed from the following directory.
- ‘C:\ProgramData\ABB’. Secure zenon_Projects directory by managing the access permissions. The project directory should have access only for the user group (Excluding administrator) which has
- the users to use zenon projects. Consider the following example:
- Example: A user group named ‘zenonOwnersGroup’ to be created and it is the only
- group that has write access to the zenon_ Projects directory. If the system has 2 users
- such as test1(Part of zenonOwnersGroup ) and test2 (not in zenonOwnersGroup ). The
- project directory (C:\Users\Public\Documents\zenon_Projects) should have write access only for the zenonOwnersGroup and for no one else. Now, test1 should have write
- access the zenon_Project directory and test2 should not.
Who should check
- Anyone running ABB Ability™ zenon >= 11 build , <= 11 build 106404
Vulnerability facts
- Affected
- ABB Ability™ zenon >= 11 build , <= 11 build 106404
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 7.0 (v3.1, CNA)CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Local
- Attack complexity: High
- Privileges required: Low
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 0.42% chance of exploitation in 30 days (percentile 28, 2026-11-26)
- CWE
- CWE-732
- Modified
Description
A vulnerability exists by allowing low-privileged users to read and update the data in various directories used by the Zenon system. An attacker could exploit the vulnerability by using specially crafted programs to exploit the vulnerabilities by allowing them to run on the zenon installed hosts. This issue affects ABB Ability™ zenon: from 11 build through 11 build 106404.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| ABB Ability™ zenon | >= 11 build , <= 11 build 106404 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2023-3322. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2023-3322.md Affected: ABB Ability™ zenon >= 11 build , <= 11 build 106404 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for ABB Ability™ zenon: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2023-3322 being exploited?
There is no confirmed exploitation: CVE-2023-3322 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.42% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2023-3322?
High: CVSS 7.0 (v3.1, scored by CNA). Not remotely exploitable (local or adjacent access needed). The attack needs conditions outside the attacker's control, which makes it harder.
Which versions are affected by CVE-2023-3322?
ABB Ability™ zenon >= 11 build , <= 11 build 106404.
Is there a fix for CVE-2023-3322?
No fixed version is listed in the sources yet. Vendor workaround: ABB recommends the following workarounds. Although these workarounds will not correct the underlying vulnerability, they block the known attack vectors. • For CVE-2023-3322, Recommended practices include that process control systems are physically protected, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed. Remove the default directory permissions for ‘Everyone’ on the service grid, ABB utilities, and zenon_Projects directories and provide access only to specific users that are expected to access zenon. Install the IIoT services, which is, the Service grid component on a separate system. Secure the ZEE600 related executable files in ‘C:\ProgramData\ABB\ABBUtilities’ directory by removing the group named “Everyone”. Ensure the group name “Everyone” should be removed from the following directory. ‘C:\ProgramData\ABB’. Secure zenon_Projects directory by managing the access permissions. The project directory should have access only for the user group (Excluding administrator) which has the users to use zenon projects. Consider the following example: Example: A user group named ‘zenonOwnersGroup’ to be created and it is the only group that has write access to the zenon_ Projects directory. If the system has 2 users such as test1(Part of zenonOwnersGroup ) and test2 (not in zenonOwnersGroup ). The project directory (C:\Users\Public\Documents\zenon_Projects) should have write access only for the zenonOwnersGroup and for no one else. Now, test1 should have write access the zenon_Project directory and test2 should not.
How do I check if I'm affected by CVE-2023-3322?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.