CVE-2023-2639
Rockwell Automation FactoryTalk System Services Vulnerable to Sensitive Information Disclosure
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Rockwell Automation FactoryTalk System Services <= 6.20
Vulnerability facts
- Affected
- Rockwell Automation FactoryTalk System Services <= 6.20
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, login needed
- CVSS
- 4.1 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:L/I:N/A:NOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: Low
- User interaction: Required
- Scope: Changed (impact reaches other components)
- Confidentiality impact: Low
- Integrity impact: None
- Availability impact: None
- EPSS
- 0.33% chance of exploitation in 30 days (percentile 19, 2026-11-26)
- CWE
- CWE-346
- Modified
Description
The underlying feedback mechanism of Rockwell Automation's FactoryTalk System Services that transfers the FactoryTalk Policy Manager rules to relevant devices on the network does not verify that the origin of the communication is from a legitimate local client device. This may allow a threat actor to craft a malicious website that, when visited, will send a malicious script that can connect to the local WebSocket endpoint and wait for events as if it was a valid client device. If successfully exploited, this would allow a threat actor to receive information including whether FactoryTalk Policy Manager is installed and potentially the entire security policy.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Rockwell Automation FactoryTalk System Services | <= 6.20 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2023-2639. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2023-2639.md Affected: Rockwell Automation FactoryTalk System Services <= 6.20 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Rockwell Automation FactoryTalk System Services: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2023-2639 being exploited?
There is no confirmed exploitation: CVE-2023-2639 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.33% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2023-2639?
Medium: CVSS 4.1 (v3.1, scored by CNA). Remote, login needed. A user has to take an action, such as opening a link, for the attack to work.
Which versions are affected by CVE-2023-2639?
Rockwell Automation FactoryTalk System Services <= 6.20.
Is there a fix for CVE-2023-2639?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2023-2639?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.