CVE-2023-1133
CVE-2023-1133
Mitigation
- Upgrade InfraSuite Device Master to 1.0.5 or later.
Who should check
- Anyone running Delta Electronics InfraSuite Device Master < 1.0.5
Vulnerability facts
- Affected
- Delta Electronics InfraSuite Device Master < 1.0.5
- Fixed in
- Delta Electronics InfraSuite Device Master 1.0.5
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- Yes: see the exploit references below
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 13.10% chance of exploitation in 30 days (percentile 97, 2026-11-26)
- CWE
- CWE-502
- Modified
Description
Delta Electronics InfraSuite Device Master versions prior to 1.0.5 contain a vulnerability in which the Device-status service listens on port 10100/ UDP by default. The service accepts the unverified UDP packets and deserializes the content, which could allow an unauthenticated attacker to remotely execute arbitrary code.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Delta Electronics InfraSuite Device Master | < 1.0.5 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2023-1133. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2023-1133.md Affected: Delta Electronics InfraSuite Device Master < 1.0.5 Fixed in: Delta Electronics InfraSuite Device Master 1.0.5 Steps: 1. Search this machine and project for Delta Electronics InfraSuite Device Master: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
Exploits and PoCs
FAQ
Is CVE-2023-1133 being exploited?
There is no confirmed exploitation: CVE-2023-1133 is not in the CISA Known Exploited Vulnerabilities catalog. Public exploit code or a proof of concept is available. EPSS estimates a 13.10% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2023-1133?
Critical: CVSS 9.8 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2023-1133?
Delta Electronics InfraSuite Device Master < 1.0.5.
Is there a fix for CVE-2023-1133?
Yes. Fixed in Delta Electronics InfraSuite Device Master 1.0.5. Upgrade InfraSuite Device Master to 1.0.5 or later.
How do I check if I'm affected by CVE-2023-1133?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.