# CVE-2023-0811: Omron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an…

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** CRITICAL 9.1
- **CVSS:** 9.1 (v3.1, CNA) `CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Privileges required: None; User interaction: None; Scope: Unchanged; Confidentiality impact: None; Integrity impact: High; Availability impact: High
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 0.81% (percentile 54, 2026-11-26)
- **CWE:** CWE-284
- **Published:** 2023-03-16T17:41:25.525Z
- **Modified:** 2026-06-17T05:26:21.667Z

## Who should check

- Anyone running Omron CJ1M SYSMAC CJ-series All versions 
- Anyone running Omron CJ1M SYSMAC CS-series All versions 
- Anyone running Omron CJ1M SYSMAC CP-series All versions 

## Description

Omron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an adversary issues a PROGRAM AREA WRITE command to a specific memory region, they could overwrite the password. This may lead to disabling UM protections or setting a non-ASCII password (non-keyboard characters) and preventing an engineer from viewing or modifying the user program.

## Affected and fixed versions

- Omron CJ1M SYSMAC CJ-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CJ-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CJ-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CJ-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CS-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)
- Omron CJ1M SYSMAC CP-series: All versions  (cvelist)

## Mitigation

- Vendor workaround: OMRON has released the following countermeasures for users to implement: 
- 
-   \*  Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit) 
-   \*  Set UM read protection password and “Prohibit from overwriting to a protected program “option. 
- 
- 
- If the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures: 
- 
- Security measures to prevent unauthorized access: 
- 
-   \*  If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures.   \*  Enable the FINS write protection function. 
-   \*  Select the Protect by IP Address 
- 
- 
- 
-   \*  Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them.  
-   \*  Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network. 
-   \*  Use a virtual private network (VPN) for remote access to control systems and equipment. 
-   \*  Use strong passwords and change them frequently. 
-   \*  Install physical controls so that only authorized personnel can access control systems and equipment. 
-   \*  Scan virus to ensure safety of any USB drives or similar devices before connecting them to systems and devices. 
-   \*  Enforce multifactor authentication to all devices with remote access to control systems and equipment whenever possible. 
-   \*  Anti-virus protection   \*  Protect any PC with access to the control system against malware and ensure installation and maintenance of up-to-date commercial grade anti-virus software protection. 
- 
- 
- 
-   \*  Data input and output protection   \*  Validation processing such as backup and range check to cope with unintentional modification of input/output data to control systems and devices. 
- 
- 
- 
-   \*  Data recovery   \*  Periodical data backup and maintenance to prepare for data loss. 
- 
- 
- 
- 
- 
- For more information, see Omron’s  Security Advisory https://www.ia.omron.com/product/vulnerability/OMSR-2023-001\_en.pdf .

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2023-0811. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2023-0811.md
Affected: Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions …
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Omron CJ1M SYSMAC CJ-series, Omron CJ1M SYSMAC CS-series, Omron CJ1M SYSMAC CP-series: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2023-0811 being exploited?

There is no confirmed exploitation: CVE-2023-0811 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.81% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2023-0811?

Critical: CVSS 9.1 (v3.1, scored by CNA). Remote, no login needed.

### Which versions are affected by CVE-2023-0811?

Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CJ-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CS-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions ; Omron CJ1M SYSMAC CP-series All versions .

### Is there a fix for CVE-2023-0811?

No fixed version is listed in the sources yet. Vendor workaround: OMRON has released the following countermeasures for users to implement:     \*  Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit)    \*  Set UM read protection password and “Prohibit from overwriting to a protected program “option.    If the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures:   Security measures to prevent unauthorized access:     \*  If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures.   \*  Enable the FINS write protection function.    \*  Select the Protect by IP Address       \*  Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them.     \*  Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network.    \*  Use a virtual private network (VPN) for remote access to control systems and equipment.    \*  Use strong passwords and change them frequently.    \*  Install physical controls so that only authorized personnel can access control systems and equipment.    \*  Scan virus to ensure safety of any USB drives or similar devices before connecting them to systems and devices.    \*  Enforce multifactor authentication to all devices with remote access to control systems and equipment whenever possible.    \*  Anti-virus protection   \*  Protect any PC with access to the control system against malware and ensure installation and maintenance of up-to-date commercial grade anti-virus software protection.       \*  Data input and output protection   \*  Validation processing such as backup and range check to cope with unintentional modification of input/output data to control systems and devices.       \*  Data recovery   \*  Periodical data backup and maintenance to prepare for data loss.       For more information, see Omron’s  Security Advisory https://www.ia.omron.com/product/vulnerability/OMSR-2023-001\_en.pdf .

### How do I check if I'm affected by CVE-2023-0811?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- vendor: <https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf>
- other: <https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2023-0811>

HTML: <https://flawdb.com/CVE-2023-0811> · JSON: <https://flawdb.com/api/v1/entries/CVE-2023-0811>