CVE-2022-45139
WAGO: Origin validation error through CORS misconfiguration
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23
- Anyone running WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23
- Anyone running WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23
- Anyone running WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23
Vulnerability facts
- Affected
- WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 5.3 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:NOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: Low
- Integrity impact: None
- Availability impact: None
- EPSS
- 0.29% chance of exploitation in 30 days (percentile 14, 2026-11-26)
- CWE
- CWE-346
- Modified
Description
A CORS Misconfiguration in the web-based management allows a malicious third party webserver to misuse all basic information pages on the webserver. In combination with CVE-2022-45138 this could lead to disclosure of device information like CPU diagnostics. As there is just a limited amount of information readable the impact only affects a small subset of confidentiality.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| WAGO Compact Controller CC100 (751-9301) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Edge Controller (752-8303/8000-002) | >= FW18, < FW22; FW23 | — | cvelist |
| WAGO PFC100 (750-81xx/xxx-xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO PFC200 (750-82xx/xxx-xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Advanced Line (762-5xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Marine Line (762-6xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Standard Line (762-4xxx) | >= FW16, < FW22; FW23 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2022-45139. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2022-45139.md Affected: WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; … Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for WAGO Compact Controller CC100 (751-9301), WAGO Edge Controller (752-8303/8000-002), WAGO PFC100 (750-81xx/xxx-xxx), WAGO PFC200 (750-82xx/xxx-xxx), WAGO Touch Panel 600 Advanced Line (762-5xxx), WAGO Touch Panel 600 Marine Line (762-6xxx): dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2022-45139 being exploited?
There is no confirmed exploitation: CVE-2022-45139 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.29% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2022-45139?
Medium: CVSS 5.3 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2022-45139?
WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23.
Is there a fix for CVE-2022-45139?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2022-45139?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.