CVE-2022-45138
WAGO: Missing Authentication for Critical Function
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23
- Anyone running WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23
- Anyone running WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23
- Anyone running WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23
- Anyone running WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23
Vulnerability facts
- Affected
- WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 0.95% chance of exploitation in 30 days (percentile 60, 2026-11-26)
- CWE
- CWE-306
- Modified
Description
The configuration backend of the web-based management can be used by unauthenticated users, although only authenticated users should be able to use the API. The vulnerability allows an unauthenticated attacker to read and set several device parameters that can lead to full compromise of the device.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| WAGO Compact Controller CC100 (751-9301) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Edge Controller (752-8303/8000-002) | >= FW18, < FW22; FW23 | — | cvelist |
| WAGO PFC100 (750-81xx/xxx-xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO PFC200 (750-82xx/xxx-xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Advanced Line (762-5xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Marine Line (762-6xxx) | >= FW16, < FW22; FW23 | — | cvelist |
| WAGO Touch Panel 600 Standard Line (762-4xxx) | >= FW16, < FW22; FW23 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2022-45138. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2022-45138.md Affected: WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; … Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for WAGO Compact Controller CC100 (751-9301), WAGO Edge Controller (752-8303/8000-002), WAGO PFC100 (750-81xx/xxx-xxx), WAGO PFC200 (750-82xx/xxx-xxx), WAGO Touch Panel 600 Advanced Line (762-5xxx), WAGO Touch Panel 600 Marine Line (762-6xxx): dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2022-45138 being exploited?
There is no confirmed exploitation: CVE-2022-45138 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.95% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2022-45138?
Critical: CVSS 9.8 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2022-45138?
WAGO Compact Controller CC100 (751-9301) >= FW16, < FW22; FW23; WAGO Edge Controller (752-8303/8000-002) >= FW18, < FW22; FW23; WAGO PFC100 (750-81xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO PFC200 (750-82xx/xxx-xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Advanced Line (762-5xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Marine Line (762-6xxx) >= FW16, < FW22; FW23; WAGO Touch Panel 600 Standard Line (762-4xxx) >= FW16, < FW22; FW23.
Is there a fix for CVE-2022-45138?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2022-45138?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.