CVE-2022-33139
A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All ve…
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Siemens Cerberus DMS All versions
- Anyone running Siemens Desigo CC All versions
- Anyone running Siemens Desigo CC Compact All versions
- Anyone running Siemens SIMATIC WinCC OA V3.16 All versions in default configuration
- Anyone running Siemens SIMATIC WinCC OA V3.17 All versions in non-default configuration
- Anyone running Siemens SIMATIC WinCC OA V3.18 All versions in non-default configuration
Vulnerability facts
- Affected
- Siemens Cerberus DMS All versions; Siemens Desigo CC All versions; Siemens Desigo CC Compact All versions; Siemens SIMATIC WinCC OA V3.16 All versions in default configuration; Siemens SIMATIC WinCC OA V3.17 All versions in non-default configuration; Siemens SIMATIC WinCC OA V3.18 All versions in non-default configuration
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.1, NVD)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 1.24% chance of exploitation in 30 days (percentile 69, 2026-11-26)
- CWE
- CWE-603
- Modified
Description
A vulnerability has been identified in Cerberus DMS (All versions), Desigo CC (All versions), Desigo CC Compact (All versions), SIMATIC WinCC OA V3.16 (All versions in default configuration), SIMATIC WinCC OA V3.17 (All versions in non-default configuration), SIMATIC WinCC OA V3.18 (All versions in non-default configuration). Affected applications use client-side only authentication, when neither server-side authentication (SSA) nor Kerberos authentication is enabled. In this configuration, attackers could impersonate other users or exploit the client-server protocol without being authenticated.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Siemens Cerberus DMS | All versions | — | cvelist |
| Siemens Desigo CC | All versions | — | cvelist |
| Siemens Desigo CC Compact | All versions | — | cvelist |
| Siemens SIMATIC WinCC OA V3.16 | All versions in default configuration | — | cvelist |
| Siemens SIMATIC WinCC OA V3.17 | All versions in non-default configuration | — | cvelist |
| Siemens SIMATIC WinCC OA V3.18 | All versions in non-default configuration | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2022-33139. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2022-33139.md Affected: Siemens Cerberus DMS All versions; Siemens Desigo CC All versions; Siemens Desigo CC Compact All versions; Siemens SIMATIC WinCC OA V3.16 All versions in default configuration; Siemens SIMATIC WinCC OA V3.17 All versions in non-default configuration; Siemens SIMATIC WinCC OA V3.18 All versions in n… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Siemens Cerberus DMS, Siemens Desigo CC, Siemens Desigo CC Compact, Siemens SIMATIC WinCC OA V3.16, Siemens SIMATIC WinCC OA V3.17, Siemens SIMATIC WinCC OA V3.18: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2022-33139 being exploited?
There is no confirmed exploitation: CVE-2022-33139 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.24% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2022-33139?
Critical: CVSS 9.8 (v3.1, scored by NVD). Remote, no login needed.
Which versions are affected by CVE-2022-33139?
Siemens Cerberus DMS All versions; Siemens Desigo CC All versions; Siemens Desigo CC Compact All versions; Siemens SIMATIC WinCC OA V3.16 All versions in default configuration; Siemens SIMATIC WinCC OA V3.17 All versions in non-default configuration; Siemens SIMATIC WinCC OA V3.18 All versions in non-default configuration.
Is there a fix for CVE-2022-33139?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2022-33139?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.