CVE-2022-2513
Cleartext Credentials Vulnerability on Hitachi Energy’s Multiple IED Connectivity Packages (IED ConnPacks) and PCM600 Products
Mitigation
- Vendor workaround: It is recommended to implement and continuously revise least privileges principles to minimize permissions and
- accesses to PCM600 related resources, included the backup file, PCMI/PCMP file.
- Recommended security
- practices and firewall configurations can help protect a process control network from attacks that originate from
- outside the network. Such practices include that process control systems are physically protected from direct
- access by unauthorized personnel, have no direct connections to the Internet, and are separated from other
- networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be
- evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or
- receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses
- before they are connected to a control system.
- An additional recommendation is to follow the hardening guidelines published by “The Center for Internet Security
- (CIS)” https://www.cisecurity.org/about-us/ to protect the host Operating System.
- More information to deploy PCM600 securely can be found in the following documents:
- 1MRS758440, PCM600 Cyber Security Deployment Guideline
Who should check
- Anyone running Hitachi Energy PCM600 >= v2.6, <= 2.11 Hotfix 20220617
- Anyone running Hitachi Energy 670 Connectivity Package >= 3.0, <= 3.4.1
- Anyone running Hitachi Energy 650 Connectivity Package >= 1.3, <= 2.4.1
- Anyone running Hitachi Energy SAM600-IO Connectivity Package >= 1.0, <= 1.2
- Anyone running Hitachi Energy GMS600 Connectivity Package >= 1.3, <= 1.3.1
- Anyone running Hitachi Energy PWC600 Connectivity Package >= 1.1, <= 1.3
Vulnerability facts
- Affected
- Hitachi Energy PCM600 >= v2.6, <= 2.11 Hotfix 20220617; Hitachi Energy 670 Connectivity Package >= 3.0, <= 3.4.1; Hitachi Energy 650 Connectivity Package >= 1.3, <= 2.4.1; Hitachi Energy SAM600-IO Connectivity Package >= 1.0, <= 1.2; Hitachi Energy GMS600 Connectivity Package >= 1.3, <= 1.3.1; Hitachi Energy PWC600 Connectivity Package >= 1.1, <= 1.3
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 7.1 (v3.1, CNA)CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:C/C:H/I:N/A:NOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Local
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Changed (impact reaches other components)
- Confidentiality impact: High
- Integrity impact: None
- Availability impact: None
- EPSS
- 0.20% chance of exploitation in 30 days (percentile 5, 2026-11-26)
- CWE
- CWE-312
- Modified
Description
A vulnerability exists in the Intelligent Electronic Device (IED) Connectivity Package (ConnPack) credential storage function in Hitachi Energy’s PCM600 product included in the versions listed below, where IEDs credentials are stored in a cleartext format in the PCM600 database and logs files. An attacker having get access to the exported backup file can exploit the vulnerability and obtain user credentials of the IEDs. Additionally, an attacker with administrator access to the PCM600 host machine can obtain other user credentials by analyzing database log files. The credentials may be used to perform unauthorized modifications such as loading incorrect configurations, reboot the IEDs or cause a denial-of-service on the IEDs.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Hitachi Energy PCM600 | >= v2.6, <= 2.11 Hotfix 20220617 | — | cvelist |
| Hitachi Energy 670 Connectivity Package | >= 3.0, <= 3.4.1 | — | cvelist |
| Hitachi Energy 650 Connectivity Package | >= 1.3, <= 2.4.1 | — | cvelist |
| Hitachi Energy SAM600-IO Connectivity Package | >= 1.0, <= 1.2 | — | cvelist |
| Hitachi Energy GMS600 Connectivity Package | >= 1.3, <= 1.3.1 | — | cvelist |
| Hitachi Energy PWC600 Connectivity Package | >= 1.1, <= 1.3 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2022-2513. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2022-2513.md Affected: Hitachi Energy PCM600 >= v2.6, <= 2.11 Hotfix 20220617; Hitachi Energy 670 Connectivity Package >= 3.0, <= 3.4.1; Hitachi Energy 650 Connectivity Package >= 1.3, <= 2.4.1; Hitachi Energy SAM600-IO Connectivity Package >= 1.0, <= 1.2; Hitachi Energy GMS600 Connectivity Package >= 1.3, <= 1.3.1; Hita… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Hitachi Energy PCM600, Hitachi Energy 670 Connectivity Package, Hitachi Energy 650 Connectivity Package, Hitachi Energy SAM600-IO Connectivity Package, Hitachi Energy GMS600 Connectivity Package, Hitachi Energy PWC600 Connectivity Package: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2022-2513 being exploited?
There is no confirmed exploitation: CVE-2022-2513 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.20% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2022-2513?
High: CVSS 7.1 (v3.1, scored by CNA). Not remotely exploitable (local or adjacent access needed).
Which versions are affected by CVE-2022-2513?
Hitachi Energy PCM600 >= v2.6, <= 2.11 Hotfix 20220617; Hitachi Energy 670 Connectivity Package >= 3.0, <= 3.4.1; Hitachi Energy 650 Connectivity Package >= 1.3, <= 2.4.1; Hitachi Energy SAM600-IO Connectivity Package >= 1.0, <= 1.2; Hitachi Energy GMS600 Connectivity Package >= 1.3, <= 1.3.1; Hitachi Energy PWC600 Connectivity Package >= 1.1, <= 1.3.
Is there a fix for CVE-2022-2513?
No fixed version is listed in the sources yet. Vendor workaround: It is recommended to implement and continuously revise least privileges principles to minimize permissions and accesses to PCM600 related resources, included the backup file, PCMI/PCMP file. Recommended security practices and firewall configurations can help protect a process control network from attacks that originate from outside the network. Such practices include that process control systems are physically protected from direct access by unauthorized personnel, have no direct connections to the Internet, and are separated from other networks by means of a firewall system that has a minimal number of ports exposed, and others that have to be evaluated case by case. Process control systems should not be used for Internet surfing, instant messaging, or receiving e-mails. Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system. An additional recommendation is to follow the hardening guidelines published by “The Center for Internet Security (CIS)” https://www.cisecurity.org/about-us/ to protect the host Operating System. More information to deploy PCM600 securely can be found in the following documents: 1MRS758440, PCM600 Cyber Security Deployment Guideline
How do I check if I'm affected by CVE-2022-2513?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.