Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2022-1797

MEDIUM 6.8EPSS 73%

Rockwell Automation Logix Controllers Uncontrolled Resource Consumption

Mitigation

  • Vendor workaround: If upgrading is not possible, Rockwell Automation recommends the following mitigations:
  • Use of Microsoft AppLocker or other similar allow list applications can help mitigate risk. Information on using AppLocker with products from Rockwell Automation is available in Knowledgebase article QA17329.
  • Confirm the least-privilege user principle is followed, and user/service account access to shared resources (such as a database) is only granted with a minimum number of rights as needed.
  • Please see Rockwell Automation’s security advisory PN1596 for more information.
  • https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559

Who should check

  • Anyone running Rockwell Automation CompactLogix 5380 controllers >= unspecified, <= 32.013
  • Anyone running Rockwell Automation Compact GuardLogix 5380 controllers >= unspecified, <= 32.013
  • Anyone running Rockwell Automation CompactLogix 5480 controllers >= unspecified, <= 32.013
  • Anyone running Rockwell Automation ControlLogix 5580 controllers >= unspecified, <= 32.013
  • Anyone running Rockwell Automation GuardLogix 5580 controllers >= unspecified, <= 32.013
  • Anyone running Rockwell Automation CompactLogix 5370 controllers >= unspecified, <= 33.013
  • Anyone running Rockwell Automation Compact GuardLogix 5370 controllers >= unspecified, <= 33.013
  • Anyone running Rockwell Automation ControlLogix 5570 controllers >= unspecified, <= 33.013

Vulnerability facts

Affected
Rockwell Automation CompactLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation Compact GuardLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation CompactLogix 5480 controllers >= unspecified, <= 32.013; Rockwell Automation ControlLogix 5580 controllers >= unspecified, <= 32.013; Rockwell Automation GuardLogix 5580 controllers >= unspecified, <= 32.013; Rockwell Automation CompactLogix 5370 controllers >= unspecified, <= 33.013; Rockwell Automation Compact GuardLogix 5370 controllers >= unspecified, <= 33.013; Rockwell Automation ControlLogix 5570 controllers >= unspecified, <= 33.013; Rockwell Automation GuardLogix 5570 controllers 33.013
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
6.8 (v3.1, CNA)CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:C/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
  • Attack vector: Network
  • Attack complexity: High
  • Privileges required: None
  • User interaction: None
  • Scope: Changed (impact reaches other components)
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: High
EPSS
1.43% chance of exploitation in 30 days (percentile 73, 2026-11-26)
CWE
CWE-400
Published
Modified

Description

A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.

Affected and fixed versions

Package / productAffectedFixedSource
Rockwell Automation CompactLogix 5380 controllers>= unspecified, <= 32.013—cvelist
Rockwell Automation Compact GuardLogix 5380 controllers>= unspecified, <= 32.013—cvelist
Rockwell Automation CompactLogix 5480 controllers>= unspecified, <= 32.013—cvelist
Rockwell Automation ControlLogix 5580 controllers>= unspecified, <= 32.013—cvelist
Rockwell Automation GuardLogix 5580 controllers>= unspecified, <= 32.013—cvelist
Rockwell Automation CompactLogix 5370 controllers>= unspecified, <= 33.013—cvelist
Rockwell Automation Compact GuardLogix 5370 controllers>= unspecified, <= 33.013—cvelist
Rockwell Automation ControlLogix 5570 controllers>= unspecified, <= 33.013—cvelist
Rockwell Automation GuardLogix 5570 controllers33.013—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2022-1797. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2022-1797.md
Affected: Rockwell Automation CompactLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation Compact GuardLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation CompactLogix 5480 controllers >= unspecified, <= 32.013; Rockwell Automation ControlLogix 5580 controllers >= unspecifi…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Rockwell Automation CompactLogix 5380 controllers, Rockwell Automation Compact GuardLogix 5380 controllers, Rockwell Automation CompactLogix 5480 controllers, Rockwell Automation ControlLogix 5580 controllers, Rockwell Automation GuardLogix 5580 controllers, Rockwell Automation CompactLogix 5370 co…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2022-1797 being exploited?

There is no confirmed exploitation: CVE-2022-1797 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.43% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2022-1797?

Medium: CVSS 6.8 (v3.1, scored by CNA). Remote, no login needed. The attack needs conditions outside the attacker's control, which makes it harder.

Which versions are affected by CVE-2022-1797?

Rockwell Automation CompactLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation Compact GuardLogix 5380 controllers >= unspecified, <= 32.013; Rockwell Automation CompactLogix 5480 controllers >= unspecified, <= 32.013; Rockwell Automation ControlLogix 5580 controllers >= unspecified, <= 32.013; Rockwell Automation GuardLogix 5580 controllers >= unspecified, <= 32.013; Rockwell Automation CompactLogix 5370 controllers >= unspecified, <= 33.013; Rockwell Automation Compact GuardLogix 5370 controllers >= unspecified, <= 33.013; Rockwell Automation ControlLogix 5570 controllers >= unspecified, <= 33.013; Rockwell Automation GuardLogix 5570 controllers 33.013.

Is there a fix for CVE-2022-1797?

No fixed version is listed in the sources yet. Vendor workaround: If upgrading is not possible, Rockwell Automation recommends the following mitigations: Use of Microsoft AppLocker or other similar allow list applications can help mitigate risk. Information on using AppLocker with products from Rockwell Automation is available in Knowledgebase article QA17329. Confirm the least-privilege user principle is followed, and user/service account access to shared resources (such as a database) is only granted with a minimum number of rights as needed. Please see Rockwell Automation’s security advisory PN1596 for more information. https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1135559

How do I check if I'm affected by CVE-2022-1797?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors