CVE-2021-40358

CRITICAL 9.9EPSS 70%

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 U…

Mitigation

  • No fix listed yet: follow the vendor advisory.

Who should check

  • Anyone running Siemens SIMATIC PCS 7 V8.2 All versions
  • Anyone running Siemens SIMATIC PCS 7 V9.0 All versions < V9.0 SP3 UC04
  • Anyone running Siemens SIMATIC PCS 7 V9.1 All versions < V9.1 SP1
  • Anyone running Siemens SIMATIC WinCC V15 and earlier All versions < V15 SP1 Update 7
  • Anyone running Siemens SIMATIC WinCC V16 All versions < V16 Update 5
  • Anyone running Siemens SIMATIC WinCC V17 All versions < V17 Update 2
  • Anyone running Siemens SIMATIC WinCC V7.4 All versions < V7.4 SP1 Update 19
  • Anyone running Siemens SIMATIC WinCC V7.5 All versions < V7.5 SP2 Update 5

Vulnerability facts

Affected
Siemens SIMATIC PCS 7 V8.2 All versions; Siemens SIMATIC PCS 7 V9.0 All versions < V9.0 SP3 UC04; Siemens SIMATIC PCS 7 V9.1 All versions < V9.1 SP1; Siemens SIMATIC WinCC V15 and earlier All versions < V15 SP1 Update 7; Siemens SIMATIC WinCC V16 All versions < V16 Update 5; Siemens SIMATIC WinCC V17 All versions < V17 Update 2; Siemens SIMATIC WinCC V7.4 All versions < V7.4 SP1 Update 19; Siemens SIMATIC WinCC V7.5 All versions < V7.5 SP2 Update 5
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, login needed
CVSS
9.9 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H/E:P/RL:O/RC:COpen in CVSS calculator
Show all 11 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: Low
  • User interaction: None
  • Scope: Changed (impact reaches other components)
  • Confidentiality impact: High
  • Integrity impact: High
  • Availability impact: High
  • E: P
  • RL: O
  • RC: C
EPSS
1.27% chance of exploitation in 30 days (percentile 70, 2026-11-26)
CWE
CWE-22
Published
Modified

Description

A vulnerability has been identified in SIMATIC PCS 7 V8.2 (All versions), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP3 UC04), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP1), SIMATIC WinCC V15 and earlier (All versions < V15 SP1 Update 7), SIMATIC WinCC V16 (All versions < V16 Update 5), SIMATIC WinCC V17 (All versions < V17 Update 2), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Update 19), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 5). Legitimate file operations on the web server of the affected systems do not properly neutralize special elements within the pathname. An attacker could then cause the pathname to resolve to a location outside of the restricted directory on the server and read, write or delete unexpected critical files.

Affected and fixed versions

Package / productAffectedFixedSource
Siemens SIMATIC PCS 7 V8.2All versions—cvelist
Siemens SIMATIC PCS 7 V9.0All versions < V9.0 SP3 UC04—cvelist
Siemens SIMATIC PCS 7 V9.1All versions < V9.1 SP1—cvelist
Siemens SIMATIC WinCC V15 and earlierAll versions < V15 SP1 Update 7—cvelist
Siemens SIMATIC WinCC V16All versions < V16 Update 5—cvelist
Siemens SIMATIC WinCC V17All versions < V17 Update 2—cvelist
Siemens SIMATIC WinCC V7.4All versions < V7.4 SP1 Update 19—cvelist
Siemens SIMATIC WinCC V7.5All versions < V7.5 SP2 Update 5—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2021-40358. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2021-40358.md
Affected: Siemens SIMATIC PCS 7 V8.2 All versions; Siemens SIMATIC PCS 7 V9.0 All versions < V9.0 SP3 UC04; Siemens SIMATIC PCS 7 V9.1 All versions < V9.1 SP1; Siemens SIMATIC WinCC V15 and earlier All versions < V15 SP1 Update 7; Siemens SIMATIC WinCC V16 All versions < V16 Update 5; Siemens SIMATIC WinCC V…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens SIMATIC PCS 7 V8.2, Siemens SIMATIC PCS 7 V9.0, Siemens SIMATIC PCS 7 V9.1, Siemens SIMATIC WinCC V15 and earlier, Siemens SIMATIC WinCC V16, Siemens SIMATIC WinCC V17: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2021-40358 being exploited?

There is no confirmed exploitation: CVE-2021-40358 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.27% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2021-40358?

Critical: CVSS 9.9 (v3.1, scored by CNA). Remote, login needed.

Which versions are affected by CVE-2021-40358?

Siemens SIMATIC PCS 7 V8.2 All versions; Siemens SIMATIC PCS 7 V9.0 All versions < V9.0 SP3 UC04; Siemens SIMATIC PCS 7 V9.1 All versions < V9.1 SP1; Siemens SIMATIC WinCC V15 and earlier All versions < V15 SP1 Update 7; Siemens SIMATIC WinCC V16 All versions < V16 Update 5; Siemens SIMATIC WinCC V17 All versions < V17 Update 2; Siemens SIMATIC WinCC V7.4 All versions < V7.4 SP1 Update 19; Siemens SIMATIC WinCC V7.5 All versions < V7.5 SP2 Update 5.

Is there a fix for CVE-2021-40358?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

How do I check if I'm affected by CVE-2021-40358?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.