CVE-2021-35533
Specially Crafted IEC 60870-5-104 Packet Vulnerability in RTU500 series
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Hitachi Energy RTU500 series >= CMU Firmware version 12.0, <= 12.0.*; >= CMU Firmware version 12.2, <= 12.2.*; >= CMU Firmware version 12.4, <= 12.4.*
Vulnerability facts
- Affected
- Hitachi Energy RTU500 series >= CMU Firmware version 12.0, <= 12.0.*; >= CMU Firmware version 12.2, <= 12.2.*; >= CMU Firmware version 12.4, <= 12.4.*
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: High
- EPSS
- 0.95% chance of exploitation in 30 days (percentile 60, 2026-11-26)
- CWE
- CWE-20
- Modified
Description
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Hitachi Energy RTU500 series | >= CMU Firmware version 12.0, <= 12.0.*; >= CMU Firmware version 12.2, <= 12.2.*; >= CMU Firmware version 12.4, <= 12.4.* | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2021-35533. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2021-35533.md Affected: Hitachi Energy RTU500 series >= CMU Firmware version 12.0, <= 12.0.*; >= CMU Firmware version 12.2, <= 12.2.*; >= CMU Firmware version 12.4, <= 12.4.* Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Hitachi Energy RTU500 series: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2021-35533 being exploited?
There is no confirmed exploitation: CVE-2021-35533 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.95% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2021-35533?
High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2021-35533?
Hitachi Energy RTU500 series >= CMU Firmware version 12.0, <= 12.0.*; >= CMU Firmware version 12.2, <= 12.2.*; >= CMU Firmware version 12.4, <= 12.4.*.
Is there a fix for CVE-2021-35533?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2021-35533?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.