CVE-2020-25197
GE Reason RT43X Clocks Code Injection
Mitigation
- Upgrade Reason RT43X Clocks to 08A06 or later.
- Vendor workaround: GE recommends users evaluate current risk and implement appropriate network security mitigation measures as follows. The following mitigation actions do not ensure complete security but should be considered until the affected time synchronization product is upgraded:
- Use strong network and physical security protection to prevent an attacker from reaching the local network where Reason RT43X clocks are normally installed.
- Block TCP/IP Ports 80 and 443 to block the HTTP/HTTPS access to web interface with Reason RT43X products, avoiding all the vulnerabilities. This TCP/IP port blocking should be limited to the Ethernet port interface where the Reason RT43X clock is connected (e.g., using Access Control List (ACL)). Otherwise, other HTTP/HTTPS applications may be affected.
- Minimize network exposure for all control system devices and/or systems and ensure they are not accessible from the Internet.
- Analyze security events to early detect unexpected traffic/communication.
Who should check
- Anyone running GE Reason RT43X Clocks >= unspecified, < 08A06
Vulnerability facts
- Affected
- GE Reason RT43X Clocks >= unspecified, < 08A06
- Fixed in
- GE Reason RT43X Clocks 08A06
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 3.17% chance of exploitation in 30 days (percentile 89, 2026-11-26)
- CWE
- CWE-94
- Modified
Description
A code injection vulnerability exists in one of the webpages in GE Reason RT430, RT431 & RT434 GNSS clocks in firmware versions prior to version 08A06 that could allow an authenticated remote attacker to execute arbitrary code on the system.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| GE Reason RT43X Clocks | >= unspecified, < 08A06 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2020-25197. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2020-25197.md Affected: GE Reason RT43X Clocks >= unspecified, < 08A06 Fixed in: GE Reason RT43X Clocks 08A06 Steps: 1. Search this machine and project for GE Reason RT43X Clocks: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2020-25197 being exploited?
There is no confirmed exploitation: CVE-2020-25197 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 3.17% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2020-25197?
Critical: CVSS 9.8 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2020-25197?
GE Reason RT43X Clocks >= unspecified, < 08A06.
Is there a fix for CVE-2020-25197?
Yes. Fixed in GE Reason RT43X Clocks 08A06. Upgrade Reason RT43X Clocks to 08A06 or later. Vendor workaround: GE recommends users evaluate current risk and implement appropriate network security mitigation measures as follows. The following mitigation actions do not ensure complete security but should be considered until the affected time synchronization product is upgraded: Use strong network and physical security protection to prevent an attacker from reaching the local network where Reason RT43X clocks are normally installed. Block TCP/IP Ports 80 and 443 to block the HTTP/HTTPS access to web interface with Reason RT43X products, avoiding all the vulnerabilities. This TCP/IP port blocking should be limited to the Ethernet port interface where the Reason RT43X clock is connected (e.g., using Access Control List (ACL)). Otherwise, other HTTP/HTTPS applications may be affected. Minimize network exposure for all control system devices and/or systems and ensure they are not accessible from the Internet. Analyze security events to early detect unexpected traffic/communication.
How do I check if I'm affected by CVE-2020-25197?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.