CVE-2020-15791
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All ve…
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions
- Anyone running Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants) All versions
- Anyone running Siemens SIMATIC WinAC RTX (F) 2010 All versions
- Anyone running Siemens SINUMERIK 840D sl All versions
Vulnerability facts
- Affected
- Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions; Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants) All versions; Siemens SIMATIC WinAC RTX (F) 2010 All versions; Siemens SINUMERIK 840D sl All versions
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Not remotely exploitable (local or adjacent access needed)
- CVSS
- 6.5 (v3.1, CNA)CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:NOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Adjacent network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: None
- Availability impact: None
- EPSS
- 0.71% chance of exploitation in 30 days (percentile 49, 2026-11-26)
- CWE
- CWE-522
- Modified
Description
A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 CPU family (incl. SIPLUS variants) (All versions), SIMATIC WinAC RTX (F) 2010 (All versions), SINUMERIK 840D sl (All versions). The authentication protocol between a client and a PLC via port 102/tcp (ISO-TSAP) insufficiently protects the transmitted password. This could allow an attacker that is able to intercept the network traffic to obtain valid PLC credentials.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) | All versions | — | cvelist |
| Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants) | All versions | — | cvelist |
| Siemens SIMATIC WinAC RTX (F) 2010 | All versions | — | cvelist |
| Siemens SINUMERIK 840D sl | All versions | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2020-15791. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2020-15791.md Affected: Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions; Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants) All versions; Siemens SIMATIC WinAC RTX (F) 2010 All versions; Siemens SINUMERIK 840D sl All versions Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants), Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants), Siemens SIMATIC WinAC RTX (F) 2010, Siemens SINUMERIK 840D sl: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
Vendor advisories
FAQ
Is CVE-2020-15791 being exploited?
There is no confirmed exploitation: CVE-2020-15791 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.71% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2020-15791?
Medium: CVSS 6.5 (v3.1, scored by CNA). Not remotely exploitable (local or adjacent access needed).
Which versions are affected by CVE-2020-15791?
Siemens SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions; Siemens SIMATIC S7-400 CPU family (incl. SIPLUS variants) All versions; Siemens SIMATIC WinAC RTX (F) 2010 All versions; Siemens SINUMERIK 840D sl All versions.
Is there a fix for CVE-2020-15791?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2020-15791?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.