CVE-2020-12526
BECKHOFF: DoS-Vulnerability for TwinCAT OPC UA Server and IPC Diagnostics UA Server
Mitigation
- Vendor workaround: Consider disabling the IPC Diagnostics Server by stopping and disabling the corresponding Windows service or service. For example this can be achieved with the following PowerShell commands:
- Stop-Service -Force -Name DevMgrSvr-UA
- Set-Service -Name DevMgrSvr-UA -StartupType Disabled
- Alternatively consider limiting access to the TCP port the OPC UA server is listening on. This can happen with a dedicated firewall appliance which sits in front of an affected device. Alternatively at the device the Windows firewall can be configured to limit access to the TCP port.
Who should check
- Anyone running Beckhoff TwinCAT OPC UA Server >= unspecified, <= 2.3.0.12
- Anyone running Beckhoff IPC Diagnostics UA Server >= unspecified, <= 3.1.0.1
- Anyone running Beckhoff TF6100 >= unspecified, <= 3.3.18
Vulnerability facts
- Affected
- Beckhoff TwinCAT OPC UA Server >= unspecified, <= 2.3.0.12; Beckhoff IPC Diagnostics UA Server >= unspecified, <= 3.1.0.1; Beckhoff TF6100 >= unspecified, <= 3.3.18
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 5.3 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:LOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: Low
- EPSS
- 0.95% chance of exploitation in 30 days (percentile 60, 2026-11-26)
- CWE
- CWE-20
- Modified
Description
TwinCAT OPC UA Server in versions up to 2.3.0.12 and IPC Diagnostics UA Server in versions up to 3.1.0.1 from Beckhoff Automation GmbH & Co. KG are vulnerable to denial of service attacks. The attacker needs to send several specifically crafted requests to the running OPC UA server. After some of these requests the OPC UA server is no longer responsive to any client. This is without effect to the real-time functionality of IPCs.
Affected and fixed versions
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2020-12526. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2020-12526.md Affected: Beckhoff TwinCAT OPC UA Server >= unspecified, <= 2.3.0.12; Beckhoff IPC Diagnostics UA Server >= unspecified, <= 3.1.0.1; Beckhoff TF6100 >= unspecified, <= 3.3.18 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Beckhoff TwinCAT OPC UA Server, Beckhoff IPC Diagnostics UA Server, Beckhoff TF6100: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
Vendor advisories
FAQ
Is CVE-2020-12526 being exploited?
There is no confirmed exploitation: CVE-2020-12526 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 0.95% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2020-12526?
Medium: CVSS 5.3 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2020-12526?
Beckhoff TwinCAT OPC UA Server >= unspecified, <= 2.3.0.12; Beckhoff IPC Diagnostics UA Server >= unspecified, <= 3.1.0.1; Beckhoff TF6100 >= unspecified, <= 3.3.18.
Is there a fix for CVE-2020-12526?
No fixed version is listed in the sources yet. Vendor workaround: Consider disabling the IPC Diagnostics Server by stopping and disabling the corresponding Windows service or service. For example this can be achieved with the following PowerShell commands: Stop-Service -Force -Name DevMgrSvr-UA Set-Service -Name DevMgrSvr-UA -StartupType Disabled Alternatively consider limiting access to the TCP port the OPC UA server is listening on. This can happen with a dedicated firewall appliance which sits in front of an affected device. Alternatively at the device the Windows firewall can be configured to limit access to the TCP port.
How do I check if I'm affected by CVE-2020-12526?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.