# CVE-2019-6575: A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 151…

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** HIGH 7.5
- **CVSS:** 7.5 (v3.1, CNA) `CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Privileges required: None; User interaction: None; Scope: Unchanged; Confidentiality impact: None; Integrity impact: None; Availability impact: High
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 1.68% (percentile 77, 2026-11-26)
- **CWE:** CWE-248
- **Published:** 2019-04-17T13:40:24.000Z
- **Modified:** 2026-06-17T02:39:17.650Z

## Who should check

- Anyone running Siemens SIMATIC CP 443-1 OPC UA All versions
- Anyone running Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) All versions \< V2.7
- Anyone running Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) All versions \< V15.1 Upd 4
- Anyone running Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) All versions \< V15.1 Upd 4
- Anyone running Siemens SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F All versions \< V15.1 Upd 4
- Anyone running Siemens SIMATIC IPC DiagMonitor All versions \< V5.1.3
- Anyone running Siemens SIMATIC NET PC Software V13 All versions
- Anyone running Siemens SIMATIC NET PC Software V14 All versions \< V14 SP1 Update 14

## Description

A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions \< V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions \< V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions \< V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions \< V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions \< V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions \< V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions \< V1.1.0), SIMATIC RF600R family (All versions \< V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions \>= V2.5 \< V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions \< V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions \< V15.1 Upd 4), SINEC NMS (All versions \< V1.0 SP1), SINEMA Server (All versions \< V14 SP2), SINUMERIK OPC UA Server (All versions \< V2.1), TeleControl Server Basic (All versions \< V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.

## Affected and fixed versions

- Siemens SIMATIC CP 443-1 OPC UA: All versions (cvelist)
- Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants): All versions \< V2.7 (cvelist)
- Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants): All versions \< V15.1 Upd 4 (cvelist)
- Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants): All versions \< V15.1 Upd 4 (cvelist)
- Siemens SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F: All versions \< V15.1 Upd 4 (cvelist)
- Siemens SIMATIC IPC DiagMonitor: All versions \< V5.1.3 (cvelist)
- Siemens SIMATIC NET PC Software V13: All versions (cvelist)
- Siemens SIMATIC NET PC Software V14: All versions \< V14 SP1 Update 14 (cvelist)
- Siemens SIMATIC NET PC Software V15: All versions (cvelist)
- Siemens SIMATIC RF188C: All versions \< V1.1.0 (cvelist)
- Siemens SIMATIC RF600R family: All versions \< V3.2.1 (cvelist)
- Siemens SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants): All versions \>= V2.5 \< V2.6.1 (cvelist)
- Siemens SIMATIC S7-1500 Software Controller: All versions between V2.5 (including) and V2.7 (excluding) (cvelist)
- Siemens SIMATIC WinCC OA: All versions \< V3.15 P018 (cvelist)
- Siemens SIMATIC WinCC Runtime Advanced: All versions \< V15.1 Upd 4 (cvelist)
- Siemens SINEC NMS: All versions \< V1.0 SP1 (cvelist)
- Siemens SINEMA Server: All versions \< V14 SP2 (cvelist)
- Siemens SINUMERIK OPC UA Server: All versions \< V2.1 (cvelist)
- Siemens TeleControl Server Basic: All versions \< V3.1.1 (cvelist)

## Mitigation

- No fix listed yet: follow the vendor advisory.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2019-6575. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2019-6575.md
Affected: Siemens SIMATIC CP 443-1 OPC UA All versions; Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) All versions < V2.7; Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) All versions < V15.1 Upd 4; Siemens SIMATIC HMI Comfort Panels 4" - 22" (inc…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens SIMATIC CP 443-1 OPC UA, Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants), Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants), Siemens SIMATIC HMI KTP Mobile Panels K…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2019-6575 being exploited?

There is no confirmed exploitation: CVE-2019-6575 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.68% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2019-6575?

High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.

### Which versions are affected by CVE-2019-6575?

Siemens SIMATIC CP 443-1 OPC UA All versions; Siemens SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) All versions \< V2.7; Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) All versions \< V15.1 Upd 4; Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) All versions \< V15.1 Upd 4; Siemens SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F All versions \< V15.1 Upd 4; Siemens SIMATIC IPC DiagMonitor All versions \< V5.1.3; Siemens SIMATIC NET PC Software V13 All versions; Siemens SIMATIC NET PC Software V14 All versions \< V14 SP1 Update 14; Siemens SIMATIC NET PC Software V15 All versions; Siemens SIMATIC RF188C All versions \< V1.1.0; Siemens SIMATIC RF600R family All versions \< V3.2.1; Siemens SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) All versions \>= V2.5 \< V2.6.1; Siemens SIMATIC S7-1500 Software Controller All versions between V2.5 (including) and V2.7 (excluding); Siemens SIMATIC WinCC OA All versions \< V3.15 P018; Siemens SIMATIC WinCC Runtime Advanced All versions \< V15.1 Upd 4; Siemens SINEC NMS All versions \< V1.0 SP1; Siemens SINEMA Server All versions \< V14 SP2; Siemens SINUMERIK OPC UA Server All versions \< V2.1; Siemens TeleControl Server Basic All versions \< V3.1.1.

### Is there a fix for CVE-2019-6575?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

### How do I check if I'm affected by CVE-2019-6575?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- vendor: <https://cert-portal.siemens.com/productcert/pdf/ssa-307392.pdf>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2019-6575>

HTML: <https://flawdb.com/CVE-2019-6575> · JSON: <https://flawdb.com/api/v1/entries/CVE-2019-6575>