Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2019-13927

MEDIUM 5.3PoCEPSS 95%

A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D wi…

Also known as EDB-47657

Mitigation

  • No fix listed yet: follow the vendor advisory.

Who should check

  • Anyone running Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 All firmware versions < V6.00.320
  • Anyone running Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 All firmware versions < V6.00.320
  • Anyone running Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server All firmware versions < V6.00.320

Vulnerability facts

Affected
Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 All firmware versions < V6.00.320; Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 All firmware versions < V6.00.320; Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server All firmware versions < V6.00.320
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
Yes: see the exploit references below
Remote exploitation
Remote, no login needed
CVSS
5.3 (v3.1, NVD)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:LOpen in CVSS calculator
Show all 8 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: None
  • User interaction: None
  • Scope: Unchanged
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: Low
EPSS
6.77% chance of exploitation in 30 days (percentile 95, 2026-11-26)
CWE
CWE-472
Published
Modified

Description

A vulnerability has been identified in Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 (All firmware versions < V6.00.320), Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server (All firmware versions < V6.00.320). The device contains a vulnerability that could allow an attacker to cause a denial of service condition on the device's web server by sending a specially crafted HTTP message to the web server port (tcp/80). The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device's web service. While the device itself stays operational, the web server responds with HTTP status code 404 (Not found) to any further request. A reboot is required to recover the web interface. At the time of advisory publication no public exploitation of this security vulnerability was known.

Affected and fixed versions

Package / productAffectedFixedSource
Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2All firmware versions < V6.00.320—cvelist
Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2All firmware versions < V6.00.320—cvelist
Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web serverAll firmware versions < V6.00.320—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2019-13927. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2019-13927.md
Affected: Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 All firmware versions < V6.00.320; Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, P…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2, Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2, Siemens AG Desigo PX auto…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2019-13927 being exploited?

There is no confirmed exploitation: CVE-2019-13927 is not in the CISA Known Exploited Vulnerabilities catalog. Public exploit code or a proof of concept is available. EPSS estimates a 6.77% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2019-13927?

Medium: CVSS 5.3 (v3.1, scored by NVD). Remote, no login needed.

Which versions are affected by CVE-2019-13927?

Siemens AG Desigo PX automation controllers PXC00-E.D, PXC50-E.D, PXC100-E.D, PXC200-E.D with Desigo PX Web modules PXA40-W0, PXA40-W1, PXA40-W2 All firmware versions < V6.00.320; Siemens AG Desigo PX automation controllers PXC00-U, PXC64-U, PXC128-U with Desigo PX Web modules PXA30-W0, PXA30-W1, PXA30-W2 All firmware versions < V6.00.320; Siemens AG Desigo PX automation controllers PXC22.1-E.D, PXC36-E.D, PXC36.1-E.D with activated web server All firmware versions < V6.00.320.

Is there a fix for CVE-2019-13927?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

How do I check if I'm affected by CVE-2019-13927?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors