CVE-2019-10953
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researcher…
Mitigation
- Vendor workaround: ABB concludes the reported behavior is not a vulnerability but is due to a misconfiguration of the PLC watchdog, which was left in the default factory settings. This has led to a configuration that does not match the expectations expressed in the test cases and the result is the PLC not reacting as intended. This misconfiguration can be fixed by setting an appropriate combination of task priority, task cycle time, and watchdog settings. Please see the “Onboard Ethernet Handling in CPU Firmware” chapter (System Technology for AC500 V2 Products > System Technology of CPU and Overall System > Onboard Technologies > Ethernet > Ethernet Protocols and Ports for AC500 V2 Products > Onboard Ethernet Handling in CPU Firmware) for further guidance.
Who should check
- Anyone running ABB 1SAP120600R0071 PM554-TP-ETH Multiple
- Anyone running Phoenix Contact 2700974 ILC 151 ETH Multiple
- Anyone running Phoenix Contact ILC 191 ETH 2TX Multiple
- Anyone running Schneider Electric Modicon M221 < v1.10.0.0
- Anyone running Schneider Electric EcoStruxure Machine Expert – Basic < v1.0
- Anyone running Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211 (versions: see the vendor advisory)
- Anyone running Siemens 6ES7314-6EH04-0AB0 Simatic S7-314 (versions: see the vendor advisory)
- Anyone running Siemens 6ED1052-1CC01-0BA8 Logo! 8 (versions: see the vendor advisory)
Vulnerability facts
- Affected
- ABB 1SAP120600R0071 PM554-TP-ETH Multiple; Phoenix Contact 2700974 ILC 151 ETH Multiple; Phoenix Contact ILC 191 ETH 2TX Multiple; Schneider Electric Modicon M221 < v1.10.0.0; Schneider Electric EcoStruxure Machine Expert – Basic < v1.0; Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211; Siemens 6ES7314-6EH04-0AB0 Simatic S7-314; Siemens 6ED1052-1CC01-0BA8 Logo! 8; WAGO 750-889 Controller KNX IP Multiple; WAGO 750-8100 Controller PFC100 Multiple; WAGO 750-880 Controller ETH Multiple; WAGO 750-831 Controller BACnet/IP Multiple
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: High
- EPSS
- 3.46% chance of exploitation in 30 days (percentile 90, 2026-11-26)
- CWE
- CWE-400
- Modified
Description
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| ABB 1SAP120600R0071 PM554-TP-ETH | Multiple | — | cvelist |
| Phoenix Contact 2700974 ILC 151 ETH | Multiple | — | cvelist |
| Phoenix Contact ILC 191 ETH 2TX | Multiple | — | cvelist |
| Schneider Electric Modicon M221 | < v1.10.0.0 | — | cvelist |
| Schneider Electric EcoStruxure Machine Expert – Basic | < v1.0 | — | cvelist |
| Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211 | — | — | cvelist |
| Siemens 6ES7314-6EH04-0AB0 Simatic S7-314 | — | — | cvelist |
| Siemens 6ED1052-1CC01-0BA8 Logo! 8 | — | — | cvelist |
| WAGO 750-889 Controller KNX IP | Multiple | — | cvelist |
| WAGO 750-8100 Controller PFC100 | Multiple | — | cvelist |
| WAGO 750-880 Controller ETH | Multiple | — | cvelist |
| WAGO 750-831 Controller BACnet/IP | Multiple | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2019-10953. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2019-10953.md Affected: ABB 1SAP120600R0071 PM554-TP-ETH Multiple; Phoenix Contact 2700974 ILC 151 ETH Multiple; Phoenix Contact ILC 191 ETH 2TX Multiple; Schneider Electric Modicon M221 < v1.10.0.0; Schneider Electric EcoStruxure Machine Expert – Basic < v1.0; Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211; Siemens 6ES7314-6… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for ABB 1SAP120600R0071 PM554-TP-ETH, Phoenix Contact 2700974 ILC 151 ETH, Phoenix Contact ILC 191 ETH 2TX, Schneider Electric Modicon M221, Schneider Electric EcoStruxure Machine Expert – Basic, Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2019-10953 being exploited?
There is no confirmed exploitation: CVE-2019-10953 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 3.46% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2019-10953?
High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2019-10953?
ABB 1SAP120600R0071 PM554-TP-ETH Multiple; Phoenix Contact 2700974 ILC 151 ETH Multiple; Phoenix Contact ILC 191 ETH 2TX Multiple; Schneider Electric Modicon M221 < v1.10.0.0; Schneider Electric EcoStruxure Machine Expert – Basic < v1.0; Siemens 6ES7211-1AE40-0XB0 Simatic S7-1211; Siemens 6ES7314-6EH04-0AB0 Simatic S7-314; Siemens 6ED1052-1CC01-0BA8 Logo! 8; WAGO 750-889 Controller KNX IP Multiple; WAGO 750-8100 Controller PFC100 Multiple; WAGO 750-880 Controller ETH Multiple; WAGO 750-831 Controller BACnet/IP Multiple.
Is there a fix for CVE-2019-10953?
No fixed version is listed in the sources yet. Vendor workaround: ABB concludes the reported behavior is not a vulnerability but is due to a misconfiguration of the PLC watchdog, which was left in the default factory settings. This has led to a configuration that does not match the expectations expressed in the test cases and the result is the PLC not reacting as intended. This misconfiguration can be fixed by setting an appropriate combination of task priority, task cycle time, and watchdog settings. Please see the “Onboard Ethernet Handling in CPU Firmware” chapter (System Technology for AC500 V2 Products > System Technology of CPU and Overall System > Onboard Technologies > Ethernet > Ethernet Protocols and Ports for AC500 V2 Products > Onboard Ethernet Handling in CPU Firmware) for further guidance.
How do I check if I'm affected by CVE-2019-10953?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.