Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2018-4838

HIGH 7.5EPSS 73%

A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet m…

Mitigation

  • No fix listed yet: follow the vendor advisory.

Who should check

  • Anyone running Siemens AG EN100 Ethernet module IEC 61850 variant All versions < V4.30
  • Anyone running Siemens AG EN100 Ethernet module DNP3 variant All versions < V1.04
  • Anyone running Siemens AG EN100 Ethernet module PROFINET IO variant All versions
  • Anyone running Siemens AG EN100 Ethernet module Modbus TCP variant All versions
  • Anyone running Siemens AG EN100 Ethernet module IEC 104 variant All versions < V1.22

Vulnerability facts

Affected
Siemens AG EN100 Ethernet module IEC 61850 variant All versions < V4.30; Siemens AG EN100 Ethernet module DNP3 variant All versions < V1.04; Siemens AG EN100 Ethernet module PROFINET IO variant All versions; Siemens AG EN100 Ethernet module Modbus TCP variant All versions; Siemens AG EN100 Ethernet module IEC 104 variant All versions < V1.22
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
7.5 (v3.0, NVD)CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:NOpen in CVSS calculator
Show all 8 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: None
  • User interaction: None
  • Scope: Unchanged
  • Confidentiality impact: None
  • Integrity impact: High
  • Availability impact: None
EPSS
1.40% chance of exploitation in 30 days (percentile 73, 2026-11-26)
CWE
CWE-306
Published
Modified

Description

A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities.

Affected and fixed versions

Package / productAffectedFixedSource
Siemens AG EN100 Ethernet module IEC 61850 variantAll versions < V4.30—cvelist
Siemens AG EN100 Ethernet module DNP3 variantAll versions < V1.04—cvelist
Siemens AG EN100 Ethernet module PROFINET IO variantAll versions—cvelist
Siemens AG EN100 Ethernet module Modbus TCP variantAll versions—cvelist
Siemens AG EN100 Ethernet module IEC 104 variantAll versions < V1.22—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2018-4838. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2018-4838.md
Affected: Siemens AG EN100 Ethernet module IEC 61850 variant All versions < V4.30; Siemens AG EN100 Ethernet module DNP3 variant All versions < V1.04; Siemens AG EN100 Ethernet module PROFINET IO variant All versions; Siemens AG EN100 Ethernet module Modbus TCP variant All versions; Siemens AG EN100 Ethernet…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens AG EN100 Ethernet module IEC 61850 variant, Siemens AG EN100 Ethernet module DNP3 variant, Siemens AG EN100 Ethernet module PROFINET IO variant, Siemens AG EN100 Ethernet module Modbus TCP variant, Siemens AG EN100 Ethernet module IEC 104 variant: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2018-4838 being exploited?

There is no confirmed exploitation: CVE-2018-4838 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.40% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2018-4838?

High: CVSS 7.5 (v3.0, scored by NVD). Remote, no login needed.

Which versions are affected by CVE-2018-4838?

Siemens AG EN100 Ethernet module IEC 61850 variant All versions < V4.30; Siemens AG EN100 Ethernet module DNP3 variant All versions < V1.04; Siemens AG EN100 Ethernet module PROFINET IO variant All versions; Siemens AG EN100 Ethernet module Modbus TCP variant All versions; Siemens AG EN100 Ethernet module IEC 104 variant All versions < V1.22.

Is there a fix for CVE-2018-4838?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

How do I check if I'm affected by CVE-2018-4838?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors