# CVE-2018-16563: A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions \< V4.35), Fir…

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** MEDIUM 5.9
- **CVSS:** 5.9 (v3.0, NVD) `CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:N/A:H`
- **CVSS metrics:** Attack vector: Network; Attack complexity: High; Privileges required: None; User interaction: None; Scope: Unchanged; Confidentiality impact: None; Integrity impact: None; Availability impact: High
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 1.16% (percentile 67, 2026-11-26)
- **Published:** 2019-03-21T14:57:36.000Z
- **Modified:** 2026-06-17T01:44:29.750Z

## Who should check

- Anyone running Siemens Firmware variant IEC 61850 for EN100 Ethernet module All versions \< V4.35
- Anyone running Siemens Firmware variant MODBUS TCP for EN100 Ethernet module All versions
- Anyone running Siemens Firmware variant DNP3 TCP for EN100 Ethernet module All versions
- Anyone running Siemens Firmware variant IEC104 for EN100 Ethernet module All versions
- Anyone running Siemens Firmware variant Profinet IO for EN100 Ethernet module All versions
- Anyone running Siemens SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules All versions \< V7.82
- Anyone running Siemens SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules All versions \< V7.58

## Description

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions \< V4.35), Firmware variant MODBUS TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions), Firmware variant Profinet IO for EN100 Ethernet module (All versions), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions \< V7.82), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions \< V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

## Affected and fixed versions

- Siemens Firmware variant IEC 61850 for EN100 Ethernet module: All versions \< V4.35 (cvelist)
- Siemens Firmware variant MODBUS TCP for EN100 Ethernet module: All versions (cvelist)
- Siemens Firmware variant DNP3 TCP for EN100 Ethernet module: All versions (cvelist)
- Siemens Firmware variant IEC104 for EN100 Ethernet module: All versions (cvelist)
- Siemens Firmware variant Profinet IO for EN100 Ethernet module: All versions (cvelist)
- Siemens SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules: All versions \< V7.82 (cvelist)
- Siemens SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules: All versions \< V7.58 (cvelist)

## Mitigation

- No fix listed yet: follow the vendor advisory.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2018-16563. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2018-16563.md
Affected: Siemens Firmware variant IEC 61850 for EN100 Ethernet module All versions < V4.35; Siemens Firmware variant MODBUS TCP for EN100 Ethernet module All versions; Siemens Firmware variant DNP3 TCP for EN100 Ethernet module All versions; Siemens Firmware variant IEC104 for EN100 Ethernet module All vers…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens Firmware variant IEC 61850 for EN100 Ethernet module, Siemens Firmware variant MODBUS TCP for EN100 Ethernet module, Siemens Firmware variant DNP3 TCP for EN100 Ethernet module, Siemens Firmware variant IEC104 for EN100 Ethernet module, Siemens Firmware variant Profinet IO for EN100 Etherne…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2018-16563 being exploited?

There is no confirmed exploitation: CVE-2018-16563 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.16% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2018-16563?

Medium: CVSS 5.9 (v3.0, scored by NVD). Remote, no login needed. The attack needs conditions outside the attacker's control, which makes it harder.

### Which versions are affected by CVE-2018-16563?

Siemens Firmware variant IEC 61850 for EN100 Ethernet module All versions \< V4.35; Siemens Firmware variant MODBUS TCP for EN100 Ethernet module All versions; Siemens Firmware variant DNP3 TCP for EN100 Ethernet module All versions; Siemens Firmware variant IEC104 for EN100 Ethernet module All versions; Siemens Firmware variant Profinet IO for EN100 Ethernet module All versions; Siemens SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules All versions \< V7.82; Siemens SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules All versions \< V7.58.

### Is there a fix for CVE-2018-16563?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

### How do I check if I'm affected by CVE-2018-16563?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- vendor: <https://cert-portal.siemens.com/productcert/pdf/ssa-104088.pdf>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2018-16563>

HTML: <https://flawdb.com/CVE-2018-16563> · JSON: <https://flawdb.com/api/v1/entries/CVE-2018-16563>