CVE-2018-16561
A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly valid…
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Siemens SIMATIC S7-300 CPUs All versions < V3.X.16
Vulnerability facts
- Affected
- Siemens SIMATIC S7-300 CPUs All versions < V3.X.16
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: High
- EPSS
- 1.40% chance of exploitation in 30 days (percentile 73, 2026-11-26)
- CWE
- CWE-20
- Modified
Description
A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Siemens SIMATIC S7-300 CPUs | All versions < V3.X.16 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2018-16561. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2018-16561.md Affected: Siemens SIMATIC S7-300 CPUs All versions < V3.X.16 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Siemens SIMATIC S7-300 CPUs: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
Vendor advisories
FAQ
Is CVE-2018-16561 being exploited?
There is no confirmed exploitation: CVE-2018-16561 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.40% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2018-16561?
High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.
Which versions are affected by CVE-2018-16561?
Siemens SIMATIC S7-300 CPUs All versions < V3.X.16.
Is there a fix for CVE-2018-16561?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2018-16561?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.