# CVE-2018-13812: A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions \< V15 Update 4), SIMATIC HMI C…

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** HIGH 7.5
- **CVSS:** 7.5 (v3.0, NVD) `CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Privileges required: None; User interaction: None; Scope: Unchanged; Confidentiality impact: High; Integrity impact: None; Availability impact: None
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 3.57% (percentile 90, 2026-11-26)
- **CWE:** CWE-22
- **Published:** 2018-12-13T16:00:00.000Z
- **Modified:** 2026-06-17T01:40:13.043Z

## Who should check

- Anyone running Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) SIMATIC HMI Comfort Panels 4" - 22" : All versions \< V15 Update 4; SIMATIC HMI Comfort Outdoor Panels 7" & 15" : All versions \< V15 Update 4; SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F : All versions \< V15 Update 4; SIMATIC WinCC Runtime Advanced : All versions \< V15 Update 4; SIMATIC WinCC Runtime Professional : All versions \< V15 Update 4; SIMATIC WinCC (TIA Portal) : All versions \< V15 Update 4; SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) : All versions

## Description

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions \< V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions \< V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions \< V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions \< V15 Update 4), SIMATIC WinCC Runtime Professional (All versions \< V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions \< V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). A directory traversal vulnerability could allow to download arbitrary files from the device. The security vulnerability could be exploited by an attacker with network access to the integrated web server. No user interaction and no authentication is required to exploit the vulnerability. The vulnerability impacts the confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

## Affected and fixed versions

- Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel): SIMATIC HMI Comfort Panels 4" - 22" : All versions \< V15 Update 4; SIMATIC HMI Comfort Outdoor Panels 7" & 15" : All versions \< V15 Update 4; SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F : All versions \< V15 Update 4; SIMATIC WinCC Runtime Advanced : All versions \< V15 Update 4; SIMATIC WinCC Runtime Professional : All versions \< V15 Update 4; SIMATIC WinCC (TIA Portal) : All versions \< V15 Update 4; SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) : All versions (cvelist)

## Mitigation

- No fix listed yet: follow the vendor advisory.

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2018-13812. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2018-13812.md
Affected: Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2018-13812 being exploited?

There is no confirmed exploitation: CVE-2018-13812 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 3.57% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2018-13812?

High: CVSS 7.5 (v3.0, scored by NVD). Remote, no login needed.

### Which versions are affected by CVE-2018-13812?

Siemens AG SIMATIC HMI Comfort Panels 4" - 22", SIMATIC HMI Comfort Outdoor Panels 7" & 15", SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F, SIMATIC WinCC Runtime Advanced, SIMATIC WinCC Runtime Professional, SIMATIC WinCC (TIA Portal), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) SIMATIC HMI Comfort Panels 4" - 22" : All versions \< V15 Update 4; SIMATIC HMI Comfort Outdoor Panels 7" & 15" : All versions \< V15 Update 4; SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 und KTP900F : All versions \< V15 Update 4; SIMATIC WinCC Runtime Advanced : All versions \< V15 Update 4; SIMATIC WinCC Runtime Professional : All versions \< V15 Update 4; SIMATIC WinCC (TIA Portal) : All versions \< V15 Update 4; SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) : All versions.

### Is there a fix for CVE-2018-13812?

No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.

### How do I check if I'm affected by CVE-2018-13812?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- vendor: <https://cert-portal.siemens.com/productcert/pdf/ssa-233109.pdf>
- other: <http://www.securityfocus.com/bid/105922>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2018-13812>

HTML: <https://flawdb.com/CVE-2018-13812> · JSON: <https://flawdb.com/api/v1/entries/CVE-2018-13812>