CVE-2018-11452
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Fir…
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module All versions < V4.33
- Anyone running Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module All versions
- Anyone running Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module All versions
- Anyone running Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module All versions
- Anyone running Siemens AG Firmware variant IEC104 for EN100 Ethernet module All versions < V1.22
Vulnerability facts
- Affected
- Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module All versions < V4.33; Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module All versions; Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module All versions; Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module All versions; Siemens AG Firmware variant IEC104 for EN100 Ethernet module All versions < V1.22
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 7.5 (v3.0, NVD)CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: None
- Integrity impact: None
- Availability impact: High
- EPSS
- 2.39% chance of exploitation in 30 days (percentile 85, 2026-11-26)
- CWE
- CWE-20
- Modified
Description
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the EN100 communication module if oscillographs are running. A manual restart is required to recover the EN100 module functionality. Successful exploitation requires an attacker with network access to send multiple packets to the EN100 module. As a precondition the IEC 61850-MMS communication needs to be activated on the affected EN100 modules. No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module | All versions < V4.33 | — | cvelist |
| Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module | All versions | — | cvelist |
| Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module | All versions | — | cvelist |
| Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module | All versions | — | cvelist |
| Siemens AG Firmware variant IEC104 for EN100 Ethernet module | All versions < V1.22 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2018-11452. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2018-11452.md Affected: Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module All versions < V4.33; Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module All versions; Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module All versions; Siemens AG Firmware variant DNP3 TCP for EN100 Etherne… Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module, Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module, Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module, Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module, Siemens AG Firmware variant IEC104 fo…: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
Patches
FAQ
Is CVE-2018-11452 being exploited?
There is no confirmed exploitation: CVE-2018-11452 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 2.39% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2018-11452?
High: CVSS 7.5 (v3.0, scored by NVD). Remote, no login needed.
Which versions are affected by CVE-2018-11452?
Siemens AG Firmware variant IEC 61850 for EN100 Ethernet module All versions < V4.33; Siemens AG Firmware variant PROFINET IO for EN100 Ethernet module All versions; Siemens AG Firmware variant Modbus TCP for EN100 Ethernet module All versions; Siemens AG Firmware variant DNP3 TCP for EN100 Ethernet module All versions; Siemens AG Firmware variant IEC104 for EN100 Ethernet module All versions < V1.22.
Is there a fix for CVE-2018-11452?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2018-11452?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.