CVE-2017-7905
A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay…
Mitigation
- No fix listed yet: follow the vendor advisory.
Who should check
- Anyone running GE Multilin SR, UR, and URplus Protective Relays GE Multilin SR, UR, and URplus Protective Relays
Vulnerability facts
- Affected
- GE Multilin SR, UR, and URplus Protective Relays GE Multilin SR, UR, and URplus Protective Relays
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.0, NVD)CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 1.28% chance of exploitation in 30 days (percentile 70, 2026-11-26)
- CWE
- CWE-261
- Modified
Description
A Weak Cryptography for Passwords issue was discovered in General Electric (GE) Multilin SR 750 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 760 Feeder Protection Relay, firmware versions prior to Version 7.47; SR 469 Motor Protection Relay, firmware versions prior to Version 5.23; SR 489 Generator Protection Relay, firmware versions prior to Version 4.06; SR 745 Transformer Protection Relay, firmware versions prior to Version 5.23; SR 369 Motor Protection Relay, all firmware versions; Multilin Universal Relay, firmware Version 6.0 and prior versions; and Multilin URplus (D90, C90, B95), all versions. Ciphertext versions of user passwords were created with a non-random initialization vector leaving them susceptible to dictionary attacks. Ciphertext of user passwords can be obtained from the front LCD panel of affected products and through issued Modbus commands.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| GE Multilin SR, UR, and URplus Protective Relays | GE Multilin SR, UR, and URplus Protective Relays | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2017-7905. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2017-7905.md Affected: GE Multilin SR, UR, and URplus Protective Relays GE Multilin SR, UR, and URplus Protective Relays Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for GE Multilin SR, UR, and URplus Protective Relays: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2017-7905 being exploited?
There is no confirmed exploitation: CVE-2017-7905 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 1.28% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2017-7905?
Critical: CVSS 9.8 (v3.0, scored by NVD). Remote, no login needed.
Which versions are affected by CVE-2017-7905?
GE Multilin SR, UR, and URplus Protective Relays GE Multilin SR, UR, and URplus Protective Relays.
Is there a fix for CVE-2017-7905?
No fixed version is listed in the sources yet. No fix listed yet: follow the vendor advisory.
How do I check if I'm affected by CVE-2017-7905?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.