Eaton’s Cooper Power Series Form 6 Control and Idea/IdeaPlus Relays with Ethernet
Mitigation
- Vendor workaround: No authentication mechanism was used for new socket connections to
- SCADA protocol listening ports on the Form 6 control and Idea/IdeaPLUS
- relays. The effects of exploiting this vulnerability are the same as the
- effects of an attacker connecting directly to the control or network
- and listening for or initiating a new session, without exploiting any
- vulnerabilities. This underscores the importance of deploying network
- segmentation and isolation on the control system network. By ensuring
- that controls are not accessible from external networks and that
- appropriate physical security measures are provided at network access
- points, risks associated with this vulnerability are greatly minimized.
- Eaton’s Cooper Power Systems recommends that asset owners using these
- products take the proper steps to ensure system wide defense-in-depth
- strategies, as outlined in Eaton’s whitepaper WP152002EN. This
- whitepaper can be downloaded at:
- https://www.eaton.com/content/dam/eaton/products/industrialcontrols-drives-automation-sensors/c441-motor-insight-motor-protection-relays/cyber-security-white-paper-wp152002en.pdf
Who should check
- Anyone running Eaton’s Cooper Power Systems Series Form 6 >= Pro View 4.0, <= Pro View 5.0
- Anyone running Eaton’s Cooper Power Systems Idea/IdeaPLUS relays >= Pro View 4.0, <= Pro View 5.0
Vulnerability facts
- Affected
- Eaton’s Cooper Power Systems Series Form 6 >= Pro View 4.0, <= Pro View 5.0; Eaton’s Cooper Power Systems Idea/IdeaPLUS relays >= Pro View 4.0, <= Pro View 5.0
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 7.6 (v2.0, CNA)AV:N/AC:H/Au:N/C:C/I:C/A:C
Show all 6 CVSS metrics
- Attack vector: Network
- Attack complexity: High
- Authentication: None
- Confidentiality impact: Complete
- Integrity impact: Complete
- Availability impact: Complete
- EPSS
- 2.49% chance of exploitation in 30 days (percentile 85, 2026-11-26)
- CWE
- CWE-342
- Modified
Description
Eaton Cooper Power Systems ProView 4.0 and 5.0 before 5.0 11 on Form 6 controls and Idea and IdeaPLUS relays generates TCP initial sequence number (ISN) values linearly, which makes it easier for remote attackers to spoof TCP sessions by predicting an ISN value.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Eaton’s Cooper Power Systems Series Form 6 | >= Pro View 4.0, <= Pro View 5.0 | — | cvelist |
| Eaton’s Cooper Power Systems Idea/IdeaPLUS relays | >= Pro View 4.0, <= Pro View 5.0 | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2014-9196. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2014-9196.md Affected: Eaton’s Cooper Power Systems Series Form 6 >= Pro View 4.0, <= Pro View 5.0; Eaton’s Cooper Power Systems Idea/IdeaPLUS relays >= Pro View 4.0, <= Pro View 5.0 Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Eaton’s Cooper Power Systems Series Form 6, Eaton’s Cooper Power Systems Idea/IdeaPLUS relays: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2014-9196 being exploited?
There is no confirmed exploitation: CVE-2014-9196 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 2.49% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2014-9196?
High: CVSS 7.6 (v2.0, scored by CNA). Remote, no login needed. The attack needs conditions outside the attacker's control, which makes it harder.
Which versions are affected by CVE-2014-9196?
Eaton’s Cooper Power Systems Series Form 6 >= Pro View 4.0, <= Pro View 5.0; Eaton’s Cooper Power Systems Idea/IdeaPLUS relays >= Pro View 4.0, <= Pro View 5.0.
Is there a fix for CVE-2014-9196?
No fixed version is listed in the sources yet. Vendor workaround: No authentication mechanism was used for new socket connections to SCADA protocol listening ports on the Form 6 control and Idea/IdeaPLUS relays. The effects of exploiting this vulnerability are the same as the effects of an attacker connecting directly to the control or network and listening for or initiating a new session, without exploiting any vulnerabilities. This underscores the importance of deploying network segmentation and isolation on the control system network. By ensuring that controls are not accessible from external networks and that appropriate physical security measures are provided at network access points, risks associated with this vulnerability are greatly minimized. Eaton’s Cooper Power Systems recommends that asset owners using these products take the proper steps to ensure system wide defense-in-depth strategies, as outlined in Eaton’s whitepaper WP152002EN. This whitepaper can be downloaded at: https://www.eaton.com/content/dam/eaton/products/industrialcontrols-drives-automation-sensors/c441-motor-insight-motor-protection-relays/cyber-security-white-paper-wp152002en.pdf
How do I check if I'm affected by CVE-2014-9196?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.