CVE-2014-5410

HIGH 7.1EPSS 92%

Rockwell Automation Micrologix 1400 Improper Input Validation

Mitigation

  • Vendor workaround: Users with Series A and Series B controllers are also recommended to apply the following risk mitigations:
  • * Do not enable DNP3 communication in the product unless required.
  • * Where appropriate, prohibit DNP3 communication that originates
  • outside the perimeter of the manufacturing zone from entry into the zone
  • by blocking communication directed at Ethernet communication Port
  • 20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a
  • firewall, UTM devices, or other security appliance)
  •           *Note: Ports 20000/TCP and 20000/UDP are factory defaults
  • as per the DNP3 specification but can be reconfigured by the product
  • owner.
  • * Employ firewalls with ingress/egress filtering, intrusion
  • detection/prevention systems, and validate all configurations. Evaluate
  • firewall configurations to ensure other appropriate inbound and outbound
  • traffic is blocked.
  • * Restrict physical and electronic access to automation products,
  • networks, and systems to only those individuals authorized to be in
  • contact with control system equipment.
  • * Employ layered security, defense-in-depth methods and network
  • segregation and segmentation practices in system design to restrict and
  • control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html http://www.ab.com/networks/architectures.html%20  for comprehensive information about implementing validated architectures designed to deliver these measures.
  • Please refer to Rockwell Automation’s product disclosure (AID 620295) for more information on this topic available at:
  • https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295

Who should check

  • Anyone running Rockwell Automation Allen-Bradley MicroLogix 1400 <= 1766-Lxxxxx Series A FRN 7; <= 1766-Lxxxxx Series B FRN 15.000

Vulnerability facts

Affected
Rockwell Automation Allen-Bradley MicroLogix 1400 <= 1766-Lxxxxx Series A FRN 7; <= 1766-Lxxxxx Series B FRN 15.000
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
7.1 (v2.0, CNA)AV:N/AC:M/Au:N/C:N/I:N/A:C
Show all 6 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Medium
  • Authentication: None
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: Complete
EPSS
4.17% chance of exploitation in 30 days (percentile 92, 2026-11-26)
CWE
CWE-20
Published
Modified

Description

The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.

Affected and fixed versions

Package / productAffectedFixedSource
Rockwell Automation Allen-Bradley MicroLogix 1400<= 1766-Lxxxxx Series A FRN 7; <= 1766-Lxxxxx Series B FRN 15.000—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2014-5410. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2014-5410.md
Affected: Rockwell Automation Allen-Bradley MicroLogix 1400 <= 1766-Lxxxxx Series A FRN 7; <= 1766-Lxxxxx Series B FRN 15.000
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Rockwell Automation Allen-Bradley MicroLogix 1400: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2014-5410 being exploited?

There is no confirmed exploitation: CVE-2014-5410 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 4.17% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2014-5410?

High: CVSS 7.1 (v2.0, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2014-5410?

Rockwell Automation Allen-Bradley MicroLogix 1400 <= 1766-Lxxxxx Series A FRN 7; <= 1766-Lxxxxx Series B FRN 15.000.

Is there a fix for CVE-2014-5410?

No fixed version is listed in the sources yet. Vendor workaround: Users with Series A and Series B controllers are also recommended to apply the following risk mitigations: * Do not enable DNP3 communication in the product unless required. * Where appropriate, prohibit DNP3 communication that originates outside the perimeter of the manufacturing zone from entry into the zone by blocking communication directed at Ethernet communication Port 20000/TCP* and 20000/UDP* using appropriate security technology (e.g., a firewall, UTM devices, or other security appliance)           *Note: Ports 20000/TCP and 20000/UDP are factory defaults as per the DNP3 specification but can be reconfigured by the product owner. * Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked. * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment. * Employ layered security, defense-in-depth methods and network segregation and segmentation practices in system design to restrict and control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html http://www.ab.com/networks/architectures.html%20  for comprehensive information about implementing validated architectures designed to deliver these measures. Please refer to Rockwell Automation’s product disclosure (AID 620295) for more information on this topic available at: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/620295

How do I check if I'm affected by CVE-2014-5410?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.