Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2014-0754

CRITICAL 10.0EPSS 96%

Schneider Electric

Mitigation

  • Vendor workaround: Search downloads for SEVD-14-260-01, then keyword SEVD-14-260-01 to
  • download the vulnerability disclosure. This URL site can also be used to
  • download firmware updates identified in the vulnerability disclosure.
  • Schneider Electric also recommends the following measures to mitigate the vulnerability for the remaining affected devices:
  • * Use a deep packet inspection firewall to prevent HTTP requests to the product that contains traversals in the URL.
  • * Disable Port 80 (HTTP) on modules where it is possible.
  • * Block Port 80 in firewalls to these devices, except for trusted devices.
  • Please contact Schneider Electric Customer Care Center for more information.

Who should check

  • Anyone running Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges 140CPU65150; 140CPU65160; 140CPU65260; 140NOC77100; 140NOC78000; 140NOC78100; 140NOE77100; 140NOE77101; 140NOE77101C; 140NOE77110; …

Vulnerability facts

Affected
Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges 140CPU65150; 140CPU65160; 140CPU65260; 140NOC77100; 140NOC78000; 140NOC78100; 140NOE77100; 140NOE77101; 140NOE77101C; 140NOE77110; …
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
10.0 (v2.0, CNA)AV:N/AC:L/Au:N/C:C/I:C/A:C
Show all 6 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Authentication: None
  • Confidentiality impact: Complete
  • Integrity impact: Complete
  • Availability impact: Complete
EPSS
9.51% chance of exploitation in 30 days (percentile 96, 2026-11-26)
CWE
CWE-22
Published
Modified

Description

Directory traversal vulnerability in SchneiderWEB on Schneider Electric Modicon PLC Ethernet modules 140CPU65x Exec before 5.5, 140NOC78x Exec before 1.62, 140NOE77x Exec before 6.2, BMXNOC0401 before 2.05, BMXNOE0100 before 2.9, BMXNOE0110x Exec before 6.0, TSXETC101 Exec before 2.04, TSXETY4103x Exec before 5.7, TSXETY5103x Exec before 5.9, TSXP57x ETYPort Exec before 5.7, and TSXP57x Ethernet Copro Exec before 5.5 allows remote attackers to visit arbitrary resources via a crafted HTTP request.

Affected and fixed versions

Package / productAffectedFixedSource
Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges140CPU65150; 140CPU65160; 140CPU65260; 140NOC77100; 140NOC78000; 140NOC78100; 140NOE77100; 140NOE77101; 140NOE77101C; 140NOE77110; …—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2014-0754. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2014-0754.md
Affected: Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges 140CPU65150; 140CPU65160; 140CPU65260; 140NOC77100; 140NOC78000; 140NOC78100; 140NOE77100; 140NOE77101; 140NOE77101C; 140NOE77110; …
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2014-0754 being exploited?

There is no confirmed exploitation: CVE-2014-0754 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 9.51% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2014-0754?

Critical: CVSS 10.0 (v2.0, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2014-0754?

Schneider Electric Ethernet modules for M340, Quantum and Premium PLC ranges 140CPU65150; 140CPU65160; 140CPU65260; 140NOC77100; 140NOC78000; 140NOC78100; 140NOE77100; 140NOE77101; 140NOE77101C; 140NOE77110; ….

Is there a fix for CVE-2014-0754?

No fixed version is listed in the sources yet. Vendor workaround: Search downloads for SEVD-14-260-01, then keyword SEVD-14-260-01 to download the vulnerability disclosure. This URL site can also be used to download firmware updates identified in the vulnerability disclosure. Schneider Electric also recommends the following measures to mitigate the vulnerability for the remaining affected devices: * Use a deep packet inspection firewall to prevent HTTP requests to the product that contains traversals in the URL. * Disable Port 80 (HTTP) on modules where it is possible. * Block Port 80 in firewalls to these devices, except for trusted devices. Please contact Schneider Electric Customer Care Center for more information.

How do I check if I'm affected by CVE-2014-0754?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.