# CVE-2012-6437: Rockwell Automation ControlLogix PLC Improper Authentication

> Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

- **Severity:** CRITICAL 9.8
- **CVSS:** 9.8 (v3.1, CNA) `CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H`
- **CVSS metrics:** Attack vector: Network; Attack complexity: Low; Privileges required: None; User interaction: None; Scope: Unchanged; Confidentiality impact: High; Integrity impact: High; Availability impact: High
- **Exploited in the wild:** Not in CISA KEV
- **Public exploit / PoC:** None known
- **Remote exploitation:** Remote, no login needed
- **EPSS:** 10.53% (percentile 96, 2026-11-26)
- **CWE:** CWE-287
- **Published:** 2013-01-24T21:00:00.000Z
- **Modified:** 2026-06-16T23:48:06.267Z

## Who should check

- Anyone running Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All
- Anyone running Rockwell Automation CompactLogix L32E and L35E controllers All
- Anyone running Rockwell Automation 1788-ENBT FLEXLogix adapter All
- Anyone running Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All
- Anyone running Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix \<= 18
- Anyone running Rockwell Automation CompactLogix and SoftLogix controllers \<= 19
- Anyone running Rockwell Automation ControlLogix and GuardLogix controllers \<= 20
- Anyone running Rockwell Automation MicroLogix 1100; 1400

## Description

The device does not properly authenticate users and the potential exists for a remote user to upload a new firmware image to the Ethernet card, whether it is a corrupt or legitimate firmware image. Successful exploitation of this vulnerability could cause loss of availability, integrity, and confidentiality and a disruption in communications with other connected devices.





Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400

## Affected and fixed versions

- Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules: All (cvelist)
- Rockwell Automation CompactLogix L32E and L35E controllers: All (cvelist)
- Rockwell Automation 1788-ENBT FLEXLogix adapter: All (cvelist)
- Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter: All (cvelist)
- Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix: \<= 18 (cvelist)
- Rockwell Automation CompactLogix and SoftLogix controllers: \<= 19 (cvelist)
- Rockwell Automation ControlLogix and GuardLogix controllers: \<= 20 (cvelist)
- Rockwell Automation MicroLogix: 1100; 1400 (cvelist)

## Mitigation

- Vendor workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products.
- 
- 
- 
- 
- 
- To mitigate the vulnerability with the Web server password authentication mechanism:
- 
-   \*  Upgrade the MicroLogix 1400 firmware to FRN 12 or higher.
-   \*  Because of limitations in the MicroLogix 1100 platform, none of the firmware updates will be able to fix this issue, so users should use the following techniques to help reduce the likelihood of compromise.
-   \*  Where possible, disable the Web server and change all default Administrator and Guest passwords.
-   \*  If Web server functionality is needed, then Rockwell recommends upgrading the product’s firmware to the most current version to have the newest enhanced protections available such as:  \*  When a controller receives two consecutive invalid authentication requests from an HTTP client, the controller resets the Authentication Counter after 60 minutes.
-   \*  When a controller receives 10 invalid authentication requests from any HTTP client, it will not accept any valid or invalid authentication packets until a 24-hour HTTP Server Lock Timer timeout.
- 
-   \*  If Web server functionality is needed, Rockwell also recommends configuring user accounts to have READ only access to the product so those accounts cannot be used to make configuration change
- In addition to the above, Rockwell recommends concerned customers remain vigilant and continue to follow security strategies that help reduce risk and enhance overall control system security. Where possible, they suggest you apply multiple recommendations and complement this list with your own best-practices:
- 
-   \*  Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to  http://www.ab.com/networks/architectures.html  for comprehensive information about implementing validated architectures designed to deliver these measures.
-   \*  Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment.
-   \*  Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked.
-   \*  Use up-to-date end-point protection software (e.g., antivirus/antimalware software) on all PC-based assets.
-   \*  Make sure that software and control system device firmware is patched to current releases.
-   \*  Periodically change passwords in control system components and infrastructure devices.
-   \*  Where applicable, set the controller key-switch/mode-switch to RUN mode.
- 
- 
- 
- 
- For more information on security with Rockwell Automation products, please refer to  Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a\_id/54102 .

## Check your systems with an agent

Paste this into a coding agent:

```text
Check whether anything I run is affected by CVE-2012-6437. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2012-6437.md
Affected: Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All; Rockwell Automation CompactLogix L32E and L35E controllers All; Rockwell Automation 1788-ENBT FLEXLogix adapter All; Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All; Rockwell Automation Control…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules, Rockwell Automation CompactLogix L32E and L35E controllers, Rockwell Automation 1788-ENBT FLEXLogix adapter, Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter, Rockwell Automation ControlLogix, CompactLo…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
```

## FAQ

### Is CVE-2012-6437 being exploited?

There is no confirmed exploitation: CVE-2012-6437 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 10.53% chance of exploitation in the next 30 days (as of 2026-11-26).

### How serious is CVE-2012-6437?

Critical: CVSS 9.8 (v3.1, scored by CNA). Remote, no login needed.

### Which versions are affected by CVE-2012-6437?

Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All; Rockwell Automation CompactLogix L32E and L35E controllers All; Rockwell Automation 1788-ENBT FLEXLogix adapter All; Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All; Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix \<= 18; Rockwell Automation CompactLogix and SoftLogix controllers \<= 19; Rockwell Automation ControlLogix and GuardLogix controllers \<= 20; Rockwell Automation MicroLogix 1100; 1400.

### Is there a fix for CVE-2012-6437?

No fixed version is listed in the sources yet. Vendor workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products.      To mitigate the vulnerability with the Web server password authentication mechanism:    \*  Upgrade the MicroLogix 1400 firmware to FRN 12 or higher.   \*  Because of limitations in the MicroLogix 1100 platform, none of the firmware updates will be able to fix this issue, so users should use the following techniques to help reduce the likelihood of compromise.   \*  Where possible, disable the Web server and change all default Administrator and Guest passwords.   \*  If Web server functionality is needed, then Rockwell recommends upgrading the product’s firmware to the most current version to have the newest enhanced protections available such as:  \*  When a controller receives two consecutive invalid authentication requests from an HTTP client, the controller resets the Authentication Counter after 60 minutes.   \*  When a controller receives 10 invalid authentication requests from any HTTP client, it will not accept any valid or invalid authentication packets until a 24-hour HTTP Server Lock Timer timeout.    \*  If Web server functionality is needed, Rockwell also recommends configuring user accounts to have READ only access to the product so those accounts cannot be used to make configuration change In addition to the above, Rockwell recommends concerned customers remain vigilant and continue to follow security strategies that help reduce risk and enhance overall control system security. Where possible, they suggest you apply multiple recommendations and complement this list with your own best-practices:    \*  Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to  http://www.ab.com/networks/architectures.html  for comprehensive information about implementing validated architectures designed to deliver these measures.   \*  Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment.   \*  Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked.   \*  Use up-to-date end-point protection software (e.g., antivirus/antimalware software) on all PC-based assets.   \*  Make sure that software and control system device firmware is patched to current releases.   \*  Periodically change passwords in control system components and infrastructure devices.   \*  Where applicable, set the controller key-switch/mode-switch to RUN mode.     For more information on security with Rockwell Automation products, please refer to  Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a\_id/54102 .

### How do I check if I'm affected by CVE-2012-6437?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

## References

- other: <https://www.cisa.gov/news-events/ics-advisories/icsa-13-011-03>
- other: <https://rockwellautomation.custhelp.com/app/answers/detail/a_id/470154>
- other: <https://rockwellautomation.custhelp.com/app/answers/detail/aid/470155>
- other: <https://rockwellautomation.custhelp.com/app/answers/detail/aid/470156>
- other: <http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102>
- other: <http://www.us-cert.gov/control_systems/pdf/ICSA-13-011-03.pdf>

## Attribution

- CVE Program: CVE® is a registered trademark of The MITRE Corporation. CVE records © 1999–2026 The MITRE Corporation. <https://www.cve.org/Legal/TermsOfUse>
- NVD: This product uses data from the NVD API but is not endorsed or certified by the NVD. <https://nvd.nist.gov/vuln/detail/CVE-2012-6437>

HTML: <https://flawdb.com/CVE-2012-6437> · JSON: <https://flawdb.com/api/v1/entries/CVE-2012-6437>