Skip to content
FlawDB
Sign in
Archived entry. Full-text search covers entries since 2026-11-10; exact IDs work for all years.

CVE-2012-6435

HIGH 7.5EPSS 99%

Rockwell Automation ControlLogix PLC Improper Access Control

Mitigation

  • Vendor workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products.
  • To mitigate the vulnerabilities pertaining to receiving valid CIP packets:
  • * Block all traffic to the Ethernet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by restricting or blocking access to TCP and UDP Ports 2222 and 44818 using appropriate security technology such as a firewall or Unified Threat Management (UTM).
  • * Employ a UTM appliance that specifically supports CIP message filtering.
  • In addition to the above, Rockwell recommends concerned customers remain vigilant and continue to follow security strategies that help reduce risk and enhance overall control system security. Where possible, they suggest you apply multiple recommendations and complement this list with your own best-practices:
  • * Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html for comprehensive information about implementing validated architectures designed to deliver these measures.
  • * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment.
  • * Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked.
  • * Use up-to-date end-point protection software (e.g., antivirus/antimalware software) on all PC-based assets.
  • * Make sure that software and control system device firmware is patched to current releases.
  • * Periodically change passwords in control system components and infrastructure devices.
  • * Where applicable, set the controller key-switch/mode-switch to RUN mode.
  • For more information on security with Rockwell Automation products, please refer to Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102 .

Who should check

  • Anyone running Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All
  • Anyone running Rockwell Automation CompactLogix L32E and L35E controllers All
  • Anyone running Rockwell Automation 1788-ENBT FLEXLogix adapter All
  • Anyone running Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All
  • Anyone running Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix <= 18
  • Anyone running Rockwell Automation CompactLogix and SoftLogix controllers <= 19
  • Anyone running Rockwell Automation ControlLogix and GuardLogix controllers <= 20
  • Anyone running Rockwell Automation MicroLogix 1100; 1400

Vulnerability facts

Affected
Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All; Rockwell Automation CompactLogix L32E and L35E controllers All; Rockwell Automation 1788-ENBT FLEXLogix adapter All; Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All; Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix <= 18; Rockwell Automation CompactLogix and SoftLogix controllers <= 19; Rockwell Automation ControlLogix and GuardLogix controllers <= 20; Rockwell Automation MicroLogix 1100; 1400
Fixed in
No fix listed yet
Exploited in the wild
Not in CISA KEV
Public exploit / PoC
None known
Remote exploitation
Remote, no login needed
CVSS
7.5 (v3.1, CNA)CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
  • Attack vector: Network
  • Attack complexity: Low
  • Privileges required: None
  • User interaction: None
  • Scope: Unchanged
  • Confidentiality impact: None
  • Integrity impact: None
  • Availability impact: High
EPSS
42.77% chance of exploitation in 30 days (percentile 99, 2026-11-26)
CWE
CWE-284
Published
Modified

Description

When an affected product receives a valid CIP message from an unauthorized or unintended source to Port 2222/TCP, Port 2222/UDP, Port 44818/TCP, or Port 44818/UDP that instructs the CPU to stop logic execution and enter a fault state, a DoS can occur. This situation could cause loss of availability and a disruption of communication with other connected devices. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400

Affected and fixed versions

Package / productAffectedFixedSource
Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modulesAll—cvelist
Rockwell Automation CompactLogix L32E and L35E controllersAll—cvelist
Rockwell Automation 1788-ENBT FLEXLogix adapterAll—cvelist
Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapterAll—cvelist
Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix<= 18—cvelist
Rockwell Automation CompactLogix and SoftLogix controllers<= 19—cvelist
Rockwell Automation ControlLogix and GuardLogix controllers<= 20—cvelist
Rockwell Automation MicroLogix1100; 1400—cvelist

Check your systems with an agent

Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.

Check whether anything I run is affected by CVE-2012-6435. Work read-only: do not install, upgrade, delete or change anything.

Details: https://flawdb.com/CVE-2012-6435.md
Affected: Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All; Rockwell Automation CompactLogix L32E and L35E controllers All; Rockwell Automation 1788-ENBT FLEXLogix adapter All; Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All; Rockwell Automation Control…
Fixed in: no fixed version listed yet

Steps:
1. Search this machine and project for Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules, Rockwell Automation CompactLogix L32E and L35E controllers, Rockwell Automation 1788-ENBT FLEXLogix adapter, Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter, Rockwell Automation ControlLogix, CompactLo…: dependency manifests and lockfiles, installed packages, container images and running services.
2. For each match, note the installed version and whether it is inside the affected range.
3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.

References

FAQ

Is CVE-2012-6435 being exploited?

There is no confirmed exploitation: CVE-2012-6435 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 42.77% chance of exploitation in the next 30 days (as of 2026-11-26).

How serious is CVE-2012-6435?

High: CVSS 7.5 (v3.1, scored by CNA). Remote, no login needed.

Which versions are affected by CVE-2012-6435?

Rockwell Automation 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules All; Rockwell Automation CompactLogix L32E and L35E controllers All; Rockwell Automation 1788-ENBT FLEXLogix adapter All; Rockwell Automation 1794-AENTR FLEX I/O EtherNet/IP adapter All; Rockwell Automation ControlLogix, CompactLogix, GuardLogix, and SoftLogix <= 18; Rockwell Automation CompactLogix and SoftLogix controllers <= 19; Rockwell Automation ControlLogix and GuardLogix controllers <= 20; Rockwell Automation MicroLogix 1100; 1400.

Is there a fix for CVE-2012-6435?

No fixed version is listed in the sources yet. Vendor workaround: Rockwell recommends updating to the newest firmware patches to fix the vulnerabilities, but if not able to do so right away, then Rockwell advises immediately employing the following mitigations for each of the affected products. To mitigate the vulnerabilities pertaining to receiving valid CIP packets: * Block all traffic to the Ethernet/IP or other CIP protocol-based devices from outside the Manufacturing Zone by restricting or blocking access to TCP and UDP Ports 2222 and 44818 using appropriate security technology such as a firewall or Unified Threat Management (UTM). * Employ a UTM appliance that specifically supports CIP message filtering. In addition to the above, Rockwell recommends concerned customers remain vigilant and continue to follow security strategies that help reduce risk and enhance overall control system security. Where possible, they suggest you apply multiple recommendations and complement this list with your own best-practices: * Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html for comprehensive information about implementing validated architectures designed to deliver these measures. * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to be in contact with control system equipment. * Employ firewalls with ingress/egress filtering, intrusion detection/prevention systems, and validate all configurations. Evaluate firewall configurations to ensure other appropriate inbound and outbound traffic is blocked. * Use up-to-date end-point protection software (e.g., antivirus/antimalware software) on all PC-based assets. * Make sure that software and control system device firmware is patched to current releases. * Periodically change passwords in control system components and infrastructure devices. * Where applicable, set the controller key-switch/mode-switch to RUN mode. For more information on security with Rockwell Automation products, please refer to Rockwell’s Security Advisory Index http://rockwellautomation.custhelp.com/app/answers/detail/a_id/54102 .

How do I check if I'm affected by CVE-2012-6435?

Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.

Sponsors