CVE-2010-5305
Rockwell PLC5/SLC5/0x/RSLogix Credentials management
Mitigation
- Vendor workaround: To help reduce the likelihood of exploitation and associated security risk, Rockwell Automation recommends the following immediate mitigation strategies (Note: multiple strategies are recommended to be employed simultaneously):
- * For PLC-5 controllers, enable and configure "Passwords and Privileges" via RSLogix 5 configuration software to restrict access to critical data and improve overall password security.
- * When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services. This functionality can be enabled via RSLogix 5 or RSLogix 500 software. (Consult Rockwell TechnoteRockwell Technote, http://rockwellautomation.custhelp.com/app/answers/detail/a_id/66678/kw/vulnerability/r_id/115100 , website last accessed January 12, 2010 for applicable firmware versions)
- * Use the latest version of RSLogix 5 or RSLogix 500 configuration software and enable FactoryTalk Security services.
- * Disable where possible the capability to perform remote programming and configuration of the product over a network to a controller by placing the controller's key switch into RUN mode.
- * For SLC controllers, enable static protection on all critical data table files to prevent any remote data changes to critical data.
- * Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html for comprehensive information about implementing validated architectures designed to deliver these measures.
- * Block all traffic to the CSP, Ethernet/IP, or other CIP protocol-based devices from outside the Manufacturing Zone by restricting or blocking access to TCP and UDP Port 2222 and Port 44818 using appropriate security technology (e.g., a firewall, UTM devices, or other security device).
- * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to make changes to control system equipment.
- * Frequently change the product’s password and obsolete previously used passwords to reduceexposure to threat from a product password becoming known.
Who should check
- Anyone running Rockwell Automation PLC5 1785-Lx; 1747-L5x
- Anyone running Rockwell Automation SLC5/0x 1785-Lx; 1747-L5x
- Anyone running Rockwell Automation RSLogix (versions: see the vendor advisory)
Vulnerability facts
- Affected
- Rockwell Automation PLC5 1785-Lx; 1747-L5x; Rockwell Automation SLC5/0x 1785-Lx; 1747-L5x; Rockwell Automation RSLogix
- Fixed in
- No fix listed yet
- Exploited in the wild
- Not in CISA KEV
- Public exploit / PoC
- None known
- Remote exploitation
- Remote, no login needed
- CVSS
- 9.8 (v3.0, NVD)CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:HOpen in CVSS calculator
Show all 8 CVSS metrics
- Attack vector: Network
- Attack complexity: Low
- Privileges required: None
- User interaction: None
- Scope: Unchanged
- Confidentiality impact: High
- Integrity impact: High
- Availability impact: High
- EPSS
- 5.70% chance of exploitation in 30 days (percentile 94, 2026-11-26)
- CWE
- CWE-255
- Modified
Description
The potential exists for exposure of the product's password used to restrict unauthorized access to Rockwell PLC5/SLC5/0x/RSLogix 1785-Lx and 1747-L5x controllers. The potential exists for an unauthorized programming and configuration client to gain access to the product and allow changes to the product’s configuration or program. When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services.
Affected and fixed versions
| Package / product | Affected | Fixed | Source |
|---|---|---|---|
| Rockwell Automation PLC5 | 1785-Lx; 1747-L5x | — | cvelist |
| Rockwell Automation SLC5/0x | 1785-Lx; 1747-L5x | — | cvelist |
| Rockwell Automation RSLogix | — | — | cvelist |
Check your systems with an agent
Paste this into Claude Code, Cursor or another coding agent. It only reads; it changes nothing.
Check whether anything I run is affected by CVE-2010-5305. Work read-only: do not install, upgrade, delete or change anything. Details: https://flawdb.com/CVE-2010-5305.md Affected: Rockwell Automation PLC5 1785-Lx; 1747-L5x; Rockwell Automation SLC5/0x 1785-Lx; 1747-L5x; Rockwell Automation RSLogix Fixed in: no fixed version listed yet Steps: 1. Search this machine and project for Rockwell Automation PLC5, Rockwell Automation SLC5/0x, Rockwell Automation RSLogix: dependency manifests and lockfiles, installed packages, container images and running services. 2. For each match, note the installed version and whether it is inside the affected range. 3. Report a table: location, installed version, affected (yes / no / unsure), evidence. If affected, say which fixed version or mitigation from the details link applies, but don't apply it.
References
FAQ
Is CVE-2010-5305 being exploited?
There is no confirmed exploitation: CVE-2010-5305 is not in the CISA Known Exploited Vulnerabilities catalog. No public exploit code is known. EPSS estimates a 5.70% chance of exploitation in the next 30 days (as of 2026-11-26).
How serious is CVE-2010-5305?
Critical: CVSS 9.8 (v3.0, scored by NVD). Remote, no login needed.
Which versions are affected by CVE-2010-5305?
Rockwell Automation PLC5 1785-Lx; 1747-L5x; Rockwell Automation SLC5/0x 1785-Lx; 1747-L5x; Rockwell Automation RSLogix.
Is there a fix for CVE-2010-5305?
No fixed version is listed in the sources yet. Vendor workaround: To help reduce the likelihood of exploitation and associated security risk, Rockwell Automation recommends the following immediate mitigation strategies (Note: multiple strategies are recommended to be employed simultaneously): * For PLC-5 controllers, enable and configure "Passwords and Privileges" via RSLogix 5 configuration software to restrict access to critical data and improve overall password security. * When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services. This functionality can be enabled via RSLogix 5 or RSLogix 500 software. (Consult Rockwell TechnoteRockwell Technote, http://rockwellautomation.custhelp.com/app/answers/detail/a_id/66678/kw/vulnerability/r_id/115100 , website last accessed January 12, 2010 for applicable firmware versions) * Use the latest version of RSLogix 5 or RSLogix 500 configuration software and enable FactoryTalk Security services. * Disable where possible the capability to perform remote programming and configuration of the product over a network to a controller by placing the controller's key switch into RUN mode. * For SLC controllers, enable static protection on all critical data table files to prevent any remote data changes to critical data. * Employ layered security and defense-in-depth methods in system design to restrict and control access to individual products and control networks. Refer to http://www.ab.com/networks/architectures.html for comprehensive information about implementing validated architectures designed to deliver these measures. * Block all traffic to the CSP, Ethernet/IP, or other CIP protocol-based devices from outside the Manufacturing Zone by restricting or blocking access to TCP and UDP Port 2222 and Port 44818 using appropriate security technology (e.g., a firewall, UTM devices, or other security device). * Restrict physical and electronic access to automation products, networks, and systems to only those individuals authorized to make changes to control system equipment. * Frequently change the product’s password and obsolete previously used passwords to reduceexposure to threat from a product password becoming known.
How do I check if I'm affected by CVE-2010-5305?
Find where you use the affected software (dependency lockfiles, installed packages, container images, servers) and compare the installed version with the affected range above. The agent prompt on this page does this read-only.